I/O <strong>Module</strong> Introduction<strong>ADAM</strong>-5081 4-ch High Speed Counter/Frequency ModeSelectionUsers can select Bi-direction, Up/Down Counter or Frequency optionas shown in Figure 55.Figure 55: Counter / Frequency ModeNote:All four channels of <strong>ADAM</strong>-5081 will operate simultaneouslyin the mode you have selected. i.e. If you switch the <strong>ADAM</strong>-5081 to Counter Mode, all four channels will operate in CounterMode.Features -- Counter ModeUp/Down CountingThe Up/Down Counter Function offers two types of counting:Up Counting (increasingly) and Down Counting (decreasingly).Up Counting: when C0A+ and C0A- sense any input signals, thecounter counts up.Down Counting: when C0B+ and C0B- sense any input signals, thecounter counts down. On receiving Up and Down signalsimultaneously, the counter will not perform each specific countingaccordingly, but will remain at the previous counting value, sincethese simultaneous signals won't have any effect on countingvalues.<strong>ADAM</strong>-<strong>5000</strong> <strong>Series</strong> I/O <strong>Module</strong> User’s <strong>Manual</strong> P.73