I/O <strong>Module</strong> IntroductionGetting the Totalizer ValueIf users want to get the actual counter value, a formula such as followscan facilitate an easy calculation from the initial counter value, overflowvalue and current counter value:Vtol = {|Vini - Vmin (or Vmax) |+ 1} x |Vvf| + |Vini - Vcur|Vtol : totalizer valueVini : initial counter valueVmin : min. counter value = 0 (fixed value)Vmax : max. counter value = 2 32 = 4,294,967,295 (fixed value)Vvf: overflow valueVcur : current counter valueExample:If the initial value =10, overflow value =4, min. value = 0, currentcounter value = 3, the totalizer value could be calculated asTotalizer value = {|10 - 0| + 1} x| 4 |+ |10 -3| = 51<strong>ADAM</strong>-<strong>5000</strong> <strong>Series</strong> I/O <strong>Module</strong> User’s <strong>Manual</strong> P.77