<strong>System</strong><strong>pro</strong> M compact ®Technical detailsCoordination tables:selectivityMCBsTmax T2 - S 200 @ 400/415 V400/415 V Supply s. T2VersionN-S-H-LRelay TM-M ELIu [A] 160 160Load s. Char. Icu [kA] In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160S 200 C 10 2 T T T T T T T T T T T T T T T T T3 T T T T T T T T T T T T T T T T T4 T T T T T T T T T T T T T T T T TB-C 10 6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T8 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T10 3* 3 3 3 4.5 7.5 8.5 T T T T T T T13 3* 3 3 4.5 7.5 7.5 T T T T T T T16 3* 3 4.5 5 7.5 T T T T T T20 3* 3 5 6 T T T T T T25 3* 5 6 T T T T T T32 3* 6 7.5 T T T T T40 5.5* 7.5 T T T T50 3* 5* 7.5 T T T63 5* T TD 10 2 T T T T T T T T T T T T T T T T T3 T T T T T T T T T T T T T T T T T4 T T T T T T T T T T T T T T T T T6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T8 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T10 3* 3 3 3 3 5 8.5 T T T T T T T13 2* 2 2 3 5 8 T T T T T16 2* 2 2 3 5 8 T T T T T20 2* 2 3 4.5 6.5 T T T T T25 2* 2.5 4 6 9.5 T T T T32 4 6 9.5 T T T T40 3* 5 8 T T T50 2* 3* 5 9.5 9.5 9.563 3* 9.5 9.5* Value valid with supply side magnetic only circuit-breaker.10Selection tables ............................... pag. 2/210/56 ABB