HIMax System 5 Programming<br />
Hardware System Variables for Setting the Parameters<br />
These <strong>system</strong> variables can be accessed in the SILworX Hardware Editor. Select the darkgray<br />
background outside the base plate symbols and double-click or use the context menu<br />
to open the Detail View.<br />
Variable Description Data type<br />
Force Deactivation ON: Forcing is deactivated.<br />
BOOL<br />
OFF: Forcing is possible.<br />
Spare 0...Spare 16<br />
Switching from OFF to ON, all forcing procedures are immediately<br />
deactivated.<br />
Default value: OFF<br />
Reserved USINT<br />
Emergency Stop 1 ... ON: It sets the controller to the STOP state<br />
BOOL<br />
Emergency Stop 4 OFF: The controller is normally running<br />
Default value: OFF<br />
Read-only in RUN ON: It locks the operator actions: Stop, Start, Download<br />
(but not Force and Reload).<br />
BOOL<br />
OFF: The operator actions: Stop, Start, Download are not<br />
locked.<br />
Default value: OFF<br />
Reload Deactivation<br />
ON: It prevents the controller from being by performing a reload.<br />
OFF: Loading by performing a reload is permitted.<br />
Default value: OFF<br />
Table 16: Hardware System Variables for Setting the Parameters<br />
i<br />
BOOL<br />
The <strong>system</strong> variables Force Deactivation, Read-only in Run and Reload Deactivation can<br />
be activated by a key switch for authorized persons.<br />
In this way, the user with the proper key switch can interrupt e.g. forcing.<br />
To make one of the <strong>system</strong> variables Force Deactivation, Read-only in Run or Reload<br />
Deactivation operable with the key switch:<br />
1. Assign a global variable to a <strong>system</strong> variable.<br />
2. Assign the same global variable to a digital input.<br />
3. Connect a key switch to the digital input..<br />
The position of the key switch defines the the <strong>system</strong> variable value.<br />
One key switch can be used to control several <strong>system</strong> variables.<br />
HI 801 001 E Rev. 3.00 Page 39 of 104