HIMax System 5 Programming<br />

Hardware System Variables for Setting the Parameters<br />

These <strong>system</strong> variables can be accessed in the SILworX Hardware Editor. Select the darkgray<br />

background outside the base plate symbols and double-click or use the context menu<br />

to open the Detail View.<br />

Variable Description Data type<br />

Force Deactivation ON: Forcing is deactivated.<br />

BOOL<br />

OFF: Forcing is possible.<br />

Spare 0...Spare 16<br />

Switching from OFF to ON, all forcing procedures are immediately<br />

deactivated.<br />

Default value: OFF<br />

Reserved USINT<br />

Emergency Stop 1 ... ON: It sets the controller to the STOP state<br />

BOOL<br />

Emergency Stop 4 OFF: The controller is normally running<br />

Default value: OFF<br />

Read-only in RUN ON: It locks the operator actions: Stop, Start, Download<br />

(but not Force and Reload).<br />

BOOL<br />

OFF: The operator actions: Stop, Start, Download are not<br />

locked.<br />

Default value: OFF<br />

Reload Deactivation<br />

ON: It prevents the controller from being by performing a reload.<br />

OFF: Loading by performing a reload is permitted.<br />

Default value: OFF<br />

Table 16: Hardware System Variables for Setting the Parameters<br />

i<br />

BOOL<br />

The <strong>system</strong> variables Force Deactivation, Read-only in Run and Reload Deactivation can<br />

be activated by a key switch for authorized persons.<br />

In this way, the user with the proper key switch can interrupt e.g. forcing.<br />

To make one of the <strong>system</strong> variables Force Deactivation, Read-only in Run or Reload<br />

Deactivation operable with the key switch:<br />

1. Assign a global variable to a <strong>system</strong> variable.<br />

2. Assign the same global variable to a digital input.<br />

3. Connect a key switch to the digital input..<br />

The position of the key switch defines the the <strong>system</strong> variable value.<br />

One key switch can be used to control several <strong>system</strong> variables.<br />

HI 801 001 E Rev. 3.00 Page 39 of 104