HIMax System 9 Life Cycle<br />

is permitted. Earthing of positive pole L+ is not permitted since a potential earth fault on the<br />

transmitter line would bypass the affected transmitter.<br />

L- can only be earthed on one place within the <strong>system</strong>. L- is usually earthed directly behind<br />

the power supply unit (e.g., on the busbar). The earthing should be easily accessible and<br />

well separable. The earthing resistance must be ≤ 2 Ω.<br />

Measures for Installing the Control Cabinet in Conformity with the CE Label<br />

In accordance with the EU Council Directive 89/336/EEC, converted in the EMC law for the<br />

Federal Republic of Germany, from the 1st January 1996, all electric equipment within the<br />

European Union must be labeled with the CE conformity marking for electromagnetic compatibility<br />

(EMC).<br />

All modules of the HIMA <strong>system</strong> family "HIMax" are labeled with the CE conformity marking.<br />

When installing controllers in control cabinets and support frames, ensure proper and interference-free<br />

electrical installation in the vicinity of the controllers to prevent EMC problems.<br />

For instance, do not lay power lines together with 24 V feed lines.<br />

Earthing the HIMA Controllers<br />

While also taking the EMC aspects into account, implement the following earthing measures<br />

to ensure the safe function of HIMA controllers.<br />

Earthing Connections<br />

All tangible surfaces of the HIMax components (e.g., base plate), except for pluggable<br />

modules, are electrically conductive (ESD protection, ESD = electrostatic discharge). Use<br />

cage nuts with claw fasteners to ensure the safe electrical connection of components such<br />

as base plates and the control cabinet. The claw fasteners penetrate the pivoting frame surface<br />

and ensure safe contact making. The screws and flat washers used are made of<br />

stainless steel to prevent electric corrosion .<br />

The components of the cabinet frame are welded together and function as electrical<br />

conductive construction element. Short earthing straps with cross-sections of 16 mm² or<br />

25 mm² are used to conductively connect the pivoting frames, door, mounting rails and, optionally,<br />

mounting plates to the cabinet frame. The earthing straps are covered with a yellow-green<br />

marking hose .The earthing straps are covered with a yellow-green marking<br />

hose .<br />