HIMax System 9 Life Cycle<br />

Pivoting Frame<br />

Screws and washers<br />

Cabinet Frame<br />

Figure 15: Earth Connections for Base Plate<br />

M 2500 Busbar, see Figure 16<br />

Earthing Strap 25 mm²<br />

The roof sheeting is secured to the cabinet frame with four lifting eyes (see Figure 16).<br />

Earth claw fasteners are used to conductively connect the side panels and the backplane<br />

to the cabinet, screws are employed to conductively secure the floor panel to the<br />

cabinet frame.<br />

Two M 2500 busbars are installed in the cabinet by default and connected to the cabinet<br />

frame with 25 mm 2 earthing straps . After removing the earthing straps, use the busbars<br />

for a earth-isolated potential (e.g., for connecting the field cable shielding).<br />

An M 8 bolt is located on the cabinet frame<br />

earth cable.<br />

to allow customers to connect the protective<br />