ONOperat<strong>in</strong>g pr<strong>in</strong>ciple of the <strong>EDS3365</strong>Direction of energyDirection of energyVoltage sourceConsumerPSA3352MESSZANGE / CLAMP ON PROBEDatenbla t / Datasheet : TGH1320Durchme ser / Diameter : 52 mmArt.-Nr. / Art.-no. : B 980 695max. 1 A600 V CAT I1000 mA / 0,1 mA ~Us2,5mAImax100mAON1 mAL1(+)AC/DCL2(-)L3PGH183Insulation fault upstreamof the current clampInsulation fault downstreamof the current clampWhen us<strong>in</strong>g the <strong>EDS3365</strong>, the direction of energy must always be taken <strong>in</strong>toaccount. This applies for the EDS mode (<strong>in</strong>sulation fault location).Insulation faults may arise up or downstream of the current clamp (or the measur<strong>in</strong>gcurrent transformer). The illustration above shows both those options. However, <strong>in</strong>the EDS mode faults can only be located DOWNSTREAM of the currentclamp.Please consider this fact when us<strong>in</strong>g <strong>EDS3365</strong>. For this reason it is advisable to startthe <strong>in</strong>sulation fault location near the voltage source <strong>in</strong> order to move towards theconsumer. This statement applies <strong>in</strong>cidentally to all <strong>in</strong>sulation fault location systems.14TGH1320E/03.2000