E110 FIREYE FLAME-MONITOR™ - Westmill Industries
E110 FIREYE FLAME-MONITOR™ - Westmill Industries
E110 FIREYE FLAME-MONITOR™ - Westmill Industries
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
2<br />
• Dipswitches located on the EP programmer to allow selectable purge time.<br />
• A run/check switch which allows the operator to stop the program sequence in any of three different<br />
positions (Purge, PTFI, or Auto).<br />
•<br />
Remote Display Capability.<br />
CAUTION: While programmers are mechanically interchangeable in that they mate with a<br />
common wiring base, you should select the correct model for your application. Inappropriate<br />
application of a control could result in an unsafe condition hazardous to life and property.<br />
Selection of a control for a particular application should be made by a competent professional,<br />
such as a boiler/burner service technician licensed by a state or other government<br />
agency.<br />
<strong>FLAME</strong>-MONITOR SPECIFICATIONS<br />
Supply Voltage: 120 VAC (+10%, -15%) 50/60 Hz<br />
Power Consumption: 25 VA<br />
Shipping Weight: (<strong>E110</strong> Approx.) 5 lbs. (2.3kg)<br />
Operating Temperature Limits:<br />
With ED500 Display: - 40°<br />
F Minimum, +125°<br />
F Maximum<br />
- 40°<br />
C Minimum, +52°<br />
C Maximum<br />
With ED510 Display: 32°<br />
F minimum, +125°<br />
F Maximum<br />
0°<br />
C Minimum, +52°<br />
C Maximum<br />
Humidity: 85% R.H. Maximum (Non-condensing)<br />
AMBIENT TEMPERATURE LIMITS<br />
®<br />
MAXIMUM MINIMUM<br />
CONTROL 140°F 60°C - 40°F - 40°C<br />
Scanner UV1A, UV2,<br />
UV8A, 45UV3<br />
200°F 93°C - 40°F - 40°C<br />
45UV5-1007, 45UV5-<br />
1009<br />
200°F 93°C - 40°F - 40°C<br />
Photocell 45CM1 165°F 74°C - 40°F - 40°C<br />
Flame Rod<br />
(Tip 2460 F)<br />
1500°F 816°C - 40°F - 40°C<br />
48PT2 125°F 52°C - 40°F - 40°C