MP 1, SQE-NE, SPA-NE, SP-NE - SCL Water
MP 1, SQE-NE, SPA-NE, SP-NE - SCL Water
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
AccessoriesSubmersible pumps<strong>SP</strong> EnvironmentalTrip classLine 1: Select IEC trip class (1 to 45).If manual indication of trip delay in the case of overloadis required, select trip class "P".Factory setting:• Cls (trip class): P.Line 2: Select trip delay.Factory setting:• Dly (trip delay): 10 s.RestartingSet whether restarting after tripping is to be• Automatic (factory setting)• Manual.Setting of time, see section “Automatic restarting”.Automatic restartingSet the time after which the <strong>MP</strong> 204 is to attemptautomatic restarting of motor after cut-out.The time runs from the moment when the value whichtriggered the fault has returned to normal.Factory setting:• 300 s.64