DigiTrace 920 Series Heat Trace Controller - Pentair Thermal ...
DigiTrace 920 Series Heat Trace Controller - Pentair Thermal ...
DigiTrace 920 Series Heat Trace Controller - Pentair Thermal ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Appendix D HTC Load Shedding SequenceLoadsheddingcommandreceived?NNormal controlmodeYHTCload shedenabled?NYAll othercontact inputsactive?[1]NYHTC holds its outputOFF for 30 secondsIscommunicationsactive?[2]NYHas HTCpower beenreset?YControl at lowtemp. alarm setpointNYFail safe modeenabled?YHTC temp. atlow temp.alarm SP?[3]NAll matching HTCs set theiroutputs to OFFHTC display indicates loadshedding mode [4]N1. If an HTC is associated with more than one contact input, all inputs must be activated beforethe HTC will go into a Load Shedding mode.2. If communications between an HTC and an upstream device such as a GCC or supervisorysoftware are interrupted, or if the power has been reset to the HTC, the HTC will hold itsoutput OFF, waiting for a Load Shedding command3. Only if the Low Temperature Alarm is ENABLED.4. For <strong>920</strong> <strong>Series</strong> controllers, a “” message will displayed after the loadcurrent reading.THERMAL MANAGEMENT SOLUTIONS EN-<strong>Digi<strong>Trace</strong></strong><strong>920</strong>series-IM-H56874 04/1373 / 82