ALARM STRUCTURECENTRALUnit_1Mod_comp1Mod_comp2Mod_comp3Mod_EvapUnit_2Mod_comp1Mod_comp2Mod_comp3Mod_EvapPUPMS – PMPRECOVERY – REC1exampleCEN : central module alarm14 : alarm identificative stringE014 : alarm descriptionCENTRAL MODULEStr Name0 E001 H2O IN temp. probe fault on control module1 E002 H2O OUT temp. probe fault on control module2 E003 Outside air temp. probe fault3 E004 Water Reset input fault4 E005 Outside RH% probe fault5 E006 Thermal cut-out alarm pump 1 on control module6 E007 Thermal cut-out alarm pump 2 on control module7 E008 Flow switch alarm on control module8 E009 System pressure alarm9 E010 Phase monitor alarm10 E011 Antifreeze alarm on control module11 E012 Antifreeze pre-alarm on control module12 E013 Change CENTRAL pump13 E014 Unit configuration alarm14 E015 Demand Limit input fault15 E016 Can net disconnectedness on control module59 E017 Inhibits control in heating60 E018 Incongruent deltaT alarm62 E019 Ext low temperature alarmM03Y40D9-01 09/04/10 page 35