Advanced Program Group (continued)A056 [Relay Out Level]Programming and Parameters 3-15Related Parameter(s): A05532 32 bit parameter.Sets the trip point for the digital output relay if the value of A055 [Relay Out Sel] is 6, 7, 8, 10 or 20.A055 Setting6781020A056 Min/Max0/240 Hz0/180%0/815 Volts0/100%0/1Values Default 0.0Min/Max: 0.0/9999Display: 0.1A067 [Accel Time 2]Related Parameter(s): P039When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart onpage 1-19 for details.Maximum Freq= Accel RateAccel TimeValues Default 20.0 SecsMin/Max:0.0/600.0 SecsDisplay:0.1 SecsP035 [Maximum Freq]SpeedAccelerationDeceleration0P039 or A067[Accel Time x]0TimeP040 or A068[Decel Time x]A068 [Decel Time 2]Related Parameter(s): P040When active, sets the rate of deceleration for all speed decreases except jog. Refer to the flowchart onpage 1-19 for details.Maximum Freq= Decel RateDecel TimeValues Default 20.0 SecsMin/Max:0.1/600.0 SecsDisplay:0.1 SecsP035 [Maximum Freq]SpeedAccelerationDeceleration0P039 or A067[Accel Time x]0TimeP040 or A068[Decel Time x]