»22« <strong>LPG</strong> DispensersFuel Gas / AUTOGAS Filling StationsCompact <strong>LPG</strong> Filling StationsFlüssiggas-AnlagenFlow Meter for <strong>LPG</strong>, Typ LPM-101, PN 25, not suitable for calibrationdesigned for retail sales dispensing unitsSystem consisting of:--with mechanical counter (only totalizing, non-resettable)flow rate 12 - 70 l/minflow direction from left ro right- without vapour eliminator, strainer, differential valve- connection 3 /4" IG NPTCertificate:- declaration of conformity with CE marking acc. to PED 97/23/ECOrder No.18 744TypeLPM-101Weight13 kg18 988 extra charge for metering package consisting of:vapour eliminator, strainer, differential valve with steel base plate,completely mounted and primed<strong>LPG</strong> Flow MeterType LPM-101Complete Metering System, Type FAS-100, PN 25, suitable for calibrationfor internal filling processes of fork lift truck and factory owned vehicles,mounted on a base plate, height 720 mm, width 700 mm, depth 260 mm,primed and paintedSystem consisting of:- with mechanical counter (Type VR) for supplied litre,resettable by handwheel, with non-resettable totalizer- without price meter- special meter for <strong>LPG</strong>flow rate 5 - 50 l/min- vapour eliminator with replaceablemicrofilter (25 µm)- connection liquid line: ball valve 1" NPT-IG- connection vapour return line: ball valve 3 /8 " NPT-IG- differential valve, outlet 3/4" NPT IGCertificate:- declaration of conformity with CE marking acc. to PED 97/23/ECOrder No. ExecutionWeight18 981 without offical calibration6018 982 with offical calibration6018 983 with pulse transmitter,56without mechanical counter,without offical calibrationNote: Pump with motor, bypass valve and strainer are located outside ofthe metering system next to the storage tank. They are not included in themetering system.<strong>LPG</strong> Metering SystemType FAS-100Electronic <strong>LPG</strong> Dispenser for busses and road tankers Type FAS-320, FAS-340 & FAS-360Housing of stainless steelElectronic:---electronic price meter, Kienzle (ER4)power supply unit 230 VAC / 50-60Hz2 LCD displays with illumination- push-button- release illuminationHydraulic PN 25:- positive displacement meter for <strong>LPG</strong>- vapour eliminator with filter unit, pressure-retaining valve, pressure gauge,diaphragm memory, back pressure check valve, relief valve 25 bar- excess flow valve before the <strong>LPG</strong> high pressure hose- <strong>LPG</strong> high pressure hose DN 16, length = 5,0 m, with breakaway coupling and<strong>LPG</strong> nozzle, type LG, with locking device (connection 1 3/4" ACME / standard)- connection liquid line: ball valve by customer specification- connection vapour return line: ball valve by customer specificationCertificate:--with PTB type approval acc. to OIML IR117<strong>LPG</strong> dispenser regulation acc. to pr EN 14678-1- declaration of conformity with CE marking acc. to PED 97/23/EC,ATEX 94/9/EC and 89/336/EWGFor Additional Price:- calibration test by an independent organisation- solenoid valve in the liquid line- control in dispenser head for electrical connection of pump motor,solenoid valve, emergency shut-off switch, etc.- hose return system<strong>LPG</strong> DispenserOrder No. Type HoseFlow Rate WeightType FAS-22022 260 FAS-320 DN 25 20 - 115 l/min 190,0additionally equipped with the22 270 FAS-340 DN 32 45 - 225 l/min 195,0hose return system, Order No. 22 40622 709 FAS-360 DN 32 76 - 300 l/min 200,0( Type FAS-320/FAS-340/FAS-360same design)Flüssiggas-Anlagen GmbH • Peiner Str. 217 • D-38229 Salzgitter/Germany • Tel. +49 (0) 5341-8697-0 • Fax +49 (0) 5341-8697-11 • www.fas-uni.de • info@fas-uni.de • © FAS 2002 071
»22«<strong>LPG</strong> DispensersFuel Gas / AUTOGAS Filling StationsCompact <strong>LPG</strong> Filling StationsFlüssiggas-AnlagenElectronic <strong>LPG</strong> Dispenser Type FAS-420, with combined car system including card system for fleetmanagement (however without Eurocard or any credit card) and incorporated receipt printerHousing of stainless steelElectronic:- with electronic price meter and precalibrated CPU board--power supply unit 230 VAC / 50-60Hzdisplay with illumination and heated- 4 MB Flash Memory Card- electronic journal- pusch-button- release illuminationHydraulic PN 25:- special meter for <strong>LPG</strong>,flow rate 5 - 50 l/min- vapour eliminator with filter unit, pressure-retaining valve, pressure gauge,diaphragm memory, back pressure check valve, relief valve 25 bar- excess flow valve before the <strong>LPG</strong> high pressure hose- <strong>LPG</strong> high pressure hose DN 16, length = 4,5 m, with breakaway coupling and<strong>LPG</strong> nozzle, type LG, with locking device (connection 1 3/4" ACME / standard)- connection liquid line: ball valve 1" NPT-IG- connection vapour return line: ball valve 3 /4 " NPT-IGCertificate:--with PTB type approval acc. to OIML IR117<strong>LPG</strong> dispenser regulation acc. to pr EN 14678-1- declaration of conformity with CE marking acc. to PED 97/23/EC,ATEX 94/9/EC and 89/336/EWGFor Additional Price:- calibration test by an independent organisation- solenoid valve in the liquid line- control in dispener head for electrical connection of pump motor,<strong>LPG</strong> Dispenser with card systemmagnetic valve, emergency shut-off switch etc.Type FAS-420Order No. Type ExecutionWeight22 871 FAS-420 standard, Meter MK-III, 1 display130,022 197 Magnetic cards, coded, available in colours red,blue, green or white, magnetic cards with specialprints (e.g. company´s logo) for publicity purposeson request. Please indicate colour when placingthe order.Electronic registration system with card reader Type FAS 400Order No. Execution22 191 Electronic registration system with card reader type FAS 400 in stand post housing,with acceptance of station cards, EC-Card, DKV/UTA, Diners and Eurocard,system for connection on all electronic FAS-<strong>LPG</strong> dispensers, with pre-calibrated CPUplate, 4 MB Flash Memory Card (emergency storage), ticket printer, illuminated andheated display, ISDN terminal adapter, execution and inscription acc. to customer´sspecification. Up to 8 pumps / dispensers may be selected, without tank data processingsoftware and hardware, with foundation frame, erection outside of the explosion proofarea, with calibration test.Notice to Electronic-Cash: For the authorization of the EC-cards or credit cards, respectivelyfleet cards the operator or customer has to contact FAS.Electronic registration system type 400 with additional CASH-operation with banknotecheck on request.22 195 Tank data processing software for FAS 400 / 420, tank data informationand accounting system „Autopoll 2000“, for Windows 95/98 with WindowsNT 4.0., individual postition for PC,menu administration / master file administration / data reading (FAS 400 / 420) /vehicle analysis / inventory maintenance / writing of invoices / data export in ASCII formatfurther processing software according to customer´s specification on request.22 966 Modem M1 (In-House) for electronic registration system FAS 400 / 420, with adapter cable,transmission of badge and tank data from the card system to the PC, without laying anddelivery of the necessary data line, for this operation 2 pieces are necessary.22 967 GSM-radio modem for electronic registration system FAS 400 / 420, complete set with antennaand connection line, GMS-M1 module on system, standard modem on PC with connection toTAE-outlet. A card contract with a mobile radiotelephone service company is necessary.22 830 Commissioning of the card system type FAS 400 / dispenser with card systemtype FAS 420, including installation of the tankdata processing software, functionalcheck and training of the service personnel with introduction of the programs.Accounting is effected according to the expenditures and according to the actualFAS installation terms.Notice: An intensive and detailled training of the service staff at site by our expertsCard Systemis necessary in order to guarantee a smooth functioning and a safe operation of theType FAS-400electronic registration system with the corresponding processing software.with additional equipment for CASHoperationwith banknote checkFor this reason this processing software has to be ordered, too. The integration intothe complete system, as well as the cabling / electrical installation of the registrationsystem and the connection to the existing hardware is to be effected by customer.Flüssiggas-Anlagen GmbH • Peiner Str. 217 • D-38229 Salzgitter/Germany • Tel. +49 (0) 5341-8697-0 • Fax +49 (0) 5341-8697-11 • www.fas-uni.de • info@fas-uni.de • © FAS 2002 072