100mm*20mmGBMGBM20mmGBMSwitchboardinstalledtotherightof a wall.(*) minimum clearance <strong>for</strong>trouble---free operation.20mmSwitchboard installed to the left ofa wall.100mm*20mmGBCGBC20mmGBCSwitchboardinstalledtotherightof a wall.(*) minimum clearance <strong>for</strong>trouble---free operation.20mmSwitchboard installed to the left ofa wall.fitting the busbars afterinstalling the cubiclesin their operating locationaccessories bag :S2: 3729742 or S6: 3729742.tools:1 torquewrench(1to50Nm.)1 1/4---3/8 adapter1 6 mm extension fitting1 6 mm male hexagonal (Allan)fitting or1 emale hexagonal socket(depending on the busbars)GBMTop busbar connections.Tightening torque : 28 Nm.Bottom busbar connections.Tightening torque : 28 Nm.18 7896779EN revision : 01