ecovery of SF6 gasat end of life<strong>for</strong> disconnector cubicleThe SF6 must be removedbe<strong>for</strong>e any dismantlingoperation can be carried out incompliance with the proceduresdescribed in IEC--61634 andaccording to the following<strong>instructions</strong>.The gas must be treated incompliance with IEC--60480.H volume of gas to berecovered: 35 litresH internal gauge pressure:40 kPANB : SF6 gas recycling at theend of circuit--breaker life, referto its instruction <strong>for</strong> <strong>use</strong>.Remove the cover (A) from thecontrol cabinet.control cover accessBRemove the control cover (B).Remove the 3 screws retaining theoperating mechanism.Cut the wiring to removethe operating mechanism.Drill 2 holes in the filler valvesafety cap∅ 4 mm, centreline 20 mm,max. depth 4 mm30 7896779EN revision : 01