LOT 4 – Telecommunications SheltersItemNumberSpecificationsSpecifications Offered (incl.brand/model)Notes,remarks, reftodocumentationEvaluationCommittee’snotesTelecommunications Shelters QTY – 101• Air and water tight to achieve IP54 levelprotection• Approximately 3m x 3m x3m in Size (minimum2.5 x 2.5 x 2.5)• Projected overhead roof of 150 mm on all sidesfor rain and snow protection• Roof loading capacity 250 kg/sq.m.• Door with mortice lock and stainless steel hinges.• Floor internal skin with 20 mm (+/-1 mm) marinegrade ply, fire retardant, fungus proof, high antistatic, anti abrasive board.• Self standing ,self supporting galvanised steelstructure• Electrical Distribution points x4, single phase• Electrical access, main RCD Breaker 25 amps• Cable access points• Internal common grounding system• Internally installed N-Type bulkhead groundingbar• Air-Conditioning minimum 1.5Kw• Internal 19” Communications rack, drilled andtapped.• Internal and external lighting.65