CATALOGUE
ZHP08C/GB -72 dpi - versione 20080916 - Zucchini
ZHP08C/GB -72 dpi - versione 20080916 - Zucchini
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Tap-off boxes<br />
EMPTY TAP-OFF BOX 125A TO 1250A : BOLT-ON TYPE<br />
Rear cable input<br />
WARNING<br />
The bolted boxes are to be installed when the busbar is disconnected and not<br />
energized.<br />
A<br />
In order to finalize the order, it is necessary to specify the type of Super Compact<br />
the box will be installed on.<br />
E<br />
Tap-off boxes can be pre-equipped with DPX moulded case circuit breakers<br />
(MCCB) upon request.<br />
C<br />
B<br />
D<br />
DIMENSIONS OF THE BOX<br />
Box rating 125A to 400A 630A 800A to 1250A<br />
(A) [mm] 365 400 450<br />
(B) [mm] 630 750 1050<br />
(C) [mm] 270 280 300<br />
(D) [mm] 95 115 115<br />
(E) [mm] 635 680 750<br />
TAP-OFF BOX WITH AC23A SWITCH DISCONNECTOR AND FUSE CARRIER, 125A TO 400A : PLUG-IN TYPE<br />
Rear cable input<br />
340<br />
Box rating Fuse Items<br />
125A NH00 65282001P<br />
250A NH1 65282002P<br />
400A NH2 65282003P<br />
550<br />
Rated insulating AC voltage Ui [V] 1000<br />
Rated impulse withstand voltage Uimp [kV] 12<br />
Type of rated duty<br />
AC23A<br />
Rated conditional short circuit current [kA] 100<br />
CEI EN 60947-3<br />
260<br />
320<br />
Can be installed and removed when the busbar is energized.<br />
To be applied on elements with any rating, with tap-off outlets.<br />
85<br />
540<br />
For operating voltages (Ue) different from 400V, please contact Zucchini.<br />
Fuses not included. See Legrand catalogue.<br />
20<br />
38 SUPER COMPACT