CATALOGUE
ZHP08C/GB -72 dpi - versione 20080916 - Zucchini
ZHP08C/GB -72 dpi - versione 20080916 - Zucchini
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SCP<br />
SUPER COMPACT<br />
Installation guidelines<br />
INSTALLATION SEQUENCE OF THE JUNCTION<br />
The installation instructions are placed on every element near the junction (Fig.1)<br />
Make sure that the contacts are clean.<br />
30 mm<br />
Join the two elements together.<br />
(Fig. 1)<br />
(Fig. 2)<br />
270 mm<br />
Make sure that the earth plate of the straight element is inserted behind the<br />
front plate of the junction monobloc (Fig.2)<br />
The positioning pin on the monobloc should be fitted into the corresponding<br />
slot on the earth plate. Verify the distance between elements, 270mm, before<br />
tightening the monobloc completely (Fig.3).<br />
(Fig. 3)<br />
Tighten the bolt of the monobloc until the 1st head breaks off (Fig. 4).<br />
The bolt that tightens the monobloc has a second head which is used when<br />
carrying out operations or inspections on the line.<br />
The nominal tightening torque is 85Nm.<br />
(Fig. 4)<br />
85Nm<br />
Install the covers of the junction (Fig. 5).<br />
(Fig. 5)<br />
Connection completed correctly with degree of protection IP55 (Fig. 6).<br />
For further information, please refer to the technical guide.<br />
(Fig. 6)<br />
51<br />
HIGH POWER GENERAL <strong>CATALOGUE</strong>