340<br />

235<br />

Technical data<br />

PE<br />

H<br />

PE<br />

H<br />

N<br />

L1 L2 L3<br />

N L1 L2 L3<br />

L1 L2 L3<br />

ALUMINIUM<br />

HR C1<br />

[3L+N 100%+PE (casing)]<br />

single bar<br />

HR C2<br />

[3L+N 50%+PE (casing)]<br />

double bar<br />

Rated current (standard installation)<br />

In [A]<br />

1000 1250 1600 2000 2250 2500 3200 4000 4500<br />

Rating for different installation<br />

Casing overall dimensions<br />

Operating/insulation voltage<br />

Frequency<br />

Rated short-time current for three-phase fault (1s)<br />

Allowable peak current for three-phase fault<br />

Rated short-time current for single-phase fault (1 s)<br />

Allowable peak current for single-phase fault<br />

Allowable specific energy for three-phase fault<br />

Phase resistance at 20° C<br />

Neutral resistance at 20 °C<br />

Phase reactance<br />

Neutral reactance<br />

Phase resistance at thermal conditions<br />

Resistance of the protective conductor<br />

Reactance of the protective conductor<br />

Resistance of the fault loop Phase-PE<br />

Reactance of the fault loop Phase-Pe (50 Hz)<br />

Resistance of the fault loop phase-neutral<br />

Reactance of the fault loop phase-neutral (50 Hz)<br />

Voltage drop factor with<br />

distributed load<br />

ΔV = k . L . I e<br />

. 10<br />

-6<br />

[V]<br />

Weight<br />

Fire load<br />

Degree of protection (CEI EN60529)<br />

Joule effect losses at rated current<br />

In [A]<br />

b x H [mm]<br />

Ue [V]<br />

f [Hz]<br />

I CW [kA]rms<br />

I pk [kA]<br />

I CW [kA]rms<br />

I pk [kA]<br />

I 2 t [MA 2 s]<br />

R 20 [mΩ/m]<br />

R 20 [mΩ/m]<br />

X [mΩ/m]<br />

X n [mΩ/m]<br />

R t [mΩ/m]<br />

R PE [mΩ/m]<br />

X PE [mΩ/m]<br />

R 0 [mΩ/m]<br />

X 0 [mΩ/m]<br />

R 0 [mΩ/m]<br />

X 0 [mΩ/m]<br />

cosϕ = 0.70<br />

cosϕ = 0.75<br />

cosϕ = 0.80<br />

cosϕ = 0.85<br />

cosϕ = 0.90<br />

cosϕ = 0.95<br />

cosϕ = 1.00<br />

p [kg/m]<br />

[kWh/m]<br />

IP<br />

P [W/m]<br />

700 875 1120 1400 1575 1750 2240 2800 3150<br />

235x171 235x221 235x221 235x251 340x171 340x221 340x221 340x251 340x271<br />

1000 1000 1000 1000 1000 1000 1000 1000 1000<br />

50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60<br />

40 50 50 60 70 90 90 90 100<br />

84 105 105 132 154 198 198 198 220<br />

24 30 30 36 42 54 54 54 60<br />

50 63 63 76 88 119 119 119 132<br />

1600 2500 2500 3600 4900 8100 8100 8100 10000<br />

0.056 0.037 0.034 0.029 0.027 0.018 0.017 0.014 0.012<br />

0.056 0.037 0.034 0.029 0.054 0.037 0.034 0.029 0.024<br />

0.087 0.066 0.066 0.053 0.049 0.034 0.034 0.024 0.024<br />

0.087 0.066 0.066 0.053 0.098 0.068 0.068 0.048 0.048<br />

0.076 0.050 0.046 0.038 0.036 0.025 0.023 0.019 0.016<br />

0.113 0.099 0.099 0.092 0.095 0.085 0.085 0.080 0.076<br />

0.130 0.130 0.130 0.130 0.110 0.110 0.110 0.110 0.110<br />

0.189 0.149 0.145 0.131 0.131 0.110 0.107 0.099 0.093<br />

0.217 0.196 0.196 0.183 0.159 0.144 0.144 0.134 0.134<br />

0.132 0.087 0.080 0.067 0.090 0.062 0.057 0.048 0.040<br />

0.217 0.196 0.196 0.183 0.208 0.178 0.178 0.158 0.158<br />

99.9 71.1 68.5 56.1 50.3 36.2 34.9 26.5 24.6<br />

99.2 70.2 65.7 55.4 51.8 35.7 34.3 26.3 24.2<br />

97.9 68.9 65.9 54.2 50.6 35.0 34.5 25.8 23.6<br />

95.6 65.8 63.8 52.5 49.1 33.9 32.4 25.1 22.8<br />

92.0 63.7 60.6 50.0 46.7 32.8 30.7 24.1 21.6<br />

86.1 58.9 55.4 46.0 43.1 28.7 23.0 22.3 18.7<br />

65.8 43.2 39.6 33.3 31.4 21.6 18.8 16.6 13.9<br />

21.2 26.2 27.1 30.0 30.8 37.9 39.5 44.0 49.0<br />

4.1 4.1 4.1 4.1 6.6 6.6 6.6 6.6 6.6<br />

30-31 30-31 30-31 30-31 30-31 30-31 30-31 30-31 30-31<br />

228 234 351 462 551 467 702 924 976<br />

k [V/m/A]10 -6 In: rated current referred to a room temperature of 40°C<br />

Product fully in compliance with the following Standards:<br />

IEC 439-1 and 2, EN 60439 part 1 and 2, DIN VDE 0660 part 500 and 502<br />

Product suitable for these climates:<br />

Constant humid climate (DIN IEC 68 / 2- 3)<br />

Cyclical humid climate (DIN IEC 68 / 2- 30)<br />

ΔV : for calculations, see page 95<br />

Contact Zucchini for the technical data tables of the other versions.<br />