29.09.2015 Views

CATALOGUE

ZHP08C/GB -72 dpi - versione 20080916 - Zucchini

ZHP08C/GB -72 dpi - versione 20080916 - Zucchini

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

HR Features<br />

HR is the Zucchini line used for transport and<br />

distribution of High Power.<br />

The applications include all industrial, commercial<br />

and service sector buildings.<br />

The HR line is available: from 1000A to 4500A<br />

with aluminium alloy conductors and up to<br />

5000A with copper conductors.<br />

HR, as all Zucchini products, is not only in<br />

compliance with the harmonised Standards<br />

CEI EN 60439-1 / 2 but it also goes beyond the<br />

required regulations: as a result, according to<br />

the manufacturer’s choice, the rated current<br />

of Zucchini’s busbar trunking systems is always<br />

referred to the average ambient temperature<br />

of 40 °C against the 35 °C required by the<br />

Standard, thus providing the markets with suitably<br />

upgraded products.<br />

The outer casing of the HR line is built with<br />

four rib-shaped C-type section metal structural<br />

components (thickness 2.0 mm), made with hot<br />

galvanized steel with processes in compliance<br />

with UNI EN 10327. The casing of the line has<br />

ventilation holes which, along with the shape of<br />

the conductors, facilitate the air circulation inside<br />

the duct as well as the heat loss generated by the<br />

Joule effect. The standard degree of protection is<br />

IP30, (IP31 on request).<br />

The busbar conductors have a rectangular<br />

cross-section with rounded corners; there are two<br />

versions:<br />

- Electrolytic copper ETP 99.9 UNI EN13601<br />

- Aluminium alloy treated over the whole<br />

surface with 5 galvanic processes<br />

(copper plating + tin plating)<br />

The insulation of the busbars is ensured by a<br />

plastic, insulating, non-desiccant double-tape<br />

with high di-electric strength and through an<br />

extended clearance.<br />

The busbar conductors are supported by plastic<br />

insulators reinforced with 20% glass fibre, with<br />

class B thermal resistance (130°C).<br />

All plastic components have a V1 self-extinguishing<br />

degree (as per UL94) and comply with the glow-wire<br />

test according to EN 60695-2-1 (CEI 50.11).<br />

The junction contact is ensured by a monobloc<br />

with shearhead bolts and two silver-plated<br />

copper plates for each phase, insulated with<br />

class F thermosetting plastic material.<br />

Finally, in order to completely verify the insulation<br />

level, every element undergoes an insulation test<br />

(phase-phase, phase-PE) with a test voltage of<br />

5000V.<br />

64 HIGH RATING

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!