Hillingdon SuDS Design & Evaluation Guide
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
9.5.4.6 Accounting for Climate Change<br />
Future predictions suggest that more<br />
extreme rainfall events will occur with greater<br />
regularity.<br />
To make allowance for this within <strong>SuDS</strong><br />
calculations the current industry approach is<br />
to factor up rainfall intensities for Climate<br />
Change Allowance.<br />
Flows in excess of the storage capacity of<br />
<strong>SuDS</strong> components should be directed along<br />
modified flow routes. When the sensitivity<br />
test indicates potential for flows across the<br />
surface, the designer should evaluate likely<br />
flood volumes, depths and velocities to<br />
ensure there is no significant risk to<br />
development or people. Generally, depths<br />
less than 0.25m will not present a risk, but<br />
steep parts of sites may generate high<br />
velocities which may be unsuitable.<br />
Table 2 from the DEFRA Guidance on climate<br />
change is replicated below with additional<br />
advisory notes on how the upper end and<br />
central projections should be applied:<br />
Detailed <strong>Design</strong><br />
<strong>Design</strong> life<br />
2015-2039<br />
<strong>Design</strong> life<br />
2040-2069<br />
<strong>Design</strong> life<br />
2070-2115<br />
Upper End Projection<br />
Carry out sensitivity test. Where<br />
unacceptable flood risk to site or<br />
adjacent sites is identified Upper<br />
End Projection allowances must be<br />
incorporated into design (i.e<br />
significant flood depths on site<br />
during this event could present a<br />
danger to people)<br />
10% 20% 40%<br />
82<br />
Central Projection<br />
These represent the Minimum<br />
climate change allowances that can<br />
be adopted where sensitivity tests<br />
demonstrate that no unacceptable<br />
flood risks are introduced by not<br />
allowing for Upper End Projections.<br />
5% 10% 20%<br />
<strong>Design</strong> Note:<br />
Climate Change should be considered for both attenuation storage and conveyance<br />
calculations.<br />
London Borough of <strong>Hillingdon</strong> <strong>SuDS</strong> D & E <strong>Guide</strong><br />
© 2018 McCloy Consulting & Robert Bray Associates