(9) Protective control function<br />

(a)<br />

(b)<br />

(c)<br />

(d)<br />

(e)<br />

Frost prevention for indoor heat exchanger (During cooling or dehumidifying)<br />

(i) Operating conditions<br />

1) Indoor heat exchanger temperature (Th2) is lower than 2.5ºC.<br />

2) 3 minutes elapsed after the start of operation.<br />

(ii) Detail of frost prevention operation<br />

Compressor<br />

Indoor fan<br />

Outdoor fan<br />

OFF<br />

Protects the fan tap just before frost prevention control.<br />

Depending on the stop mode<br />

(iii) Reset condition: Indoor heat exchanger temperature (Th2) is higher than 15ºC.<br />

Indoor fan motor protection<br />

When the airconditioner is operating and the indoor fan motor is turned ON, if the indoor fan motor has operated at 300 min -1 or<br />

under for more than 30 seconds, the unit enters first in the stop mode and then stops the entire system.<br />

TIMER light illuminates simultaneously and the RUN light flashing 6-time at each 8-second.<br />

3 minutes forced operation<br />

When the compressor begins operating the thermal operation is not effective for 3 minutes, so operation continues as is in the<br />

operation mode. (After 3 minutes has passed the thermal operation is effective.)<br />

However, stopping the compressor via a stop signal or protection control has priority.<br />

Abnormality of outdoor unit<br />

After the compressor run 5 minutes, and the indoor heat exchanger temperature more than 25ºC continuously more than 40 minutes,<br />

then the abnormality stop occurs.<br />

Sensor disconnection (room temperature, indoor heat exchanger)<br />

(i)<br />

(ii)<br />

Room temperature sensor<br />

If the temperature detected by the room temperature sensor is – 45ºC or lower, continuously for 15 seconds or longer, then<br />

operation is stopped, an error indication is displayed. (RUN light: 2-time flash, TIMER light: ON)<br />

Indoor heat exchanger temperature sensor<br />

If the temperature detected by the indoor heat exchanger temperature sensor is –28ºC or lower, continuously for 15 seconds<br />

or longer, then operation is stopped, an error indication is displayed.<br />

(RUN light : 1-time flash, TIMER light : ON)<br />

- 61 - '15 • SRK-T-171