(6) Inspection procedures corresponding to detail of trouble<br />

Sensor error<br />

Is connector connection good?<br />

YES<br />

Is sensor resistance value good?<br />

(Broken wire) 30<br />

(Short circuit)<br />

YES<br />

Replace PCB.<br />

NO<br />

NO<br />

◆ Sensor temperature characteristics<br />

(Room temp., indoor heat exchanger temp.)<br />

Resistance (kΩ)<br />

25<br />

20<br />

15<br />

10<br />

5<br />

-10<br />

0<br />

10 20 30 40 50 60 70<br />

Temperature (˚C)<br />

Indoor fan motor error<br />

Is connector connection good?<br />

YES<br />

Is the output of the indoor unit<br />

PCB normal?<br />

Power source reset<br />

Is normal state restored?<br />

YES<br />

Malfunction by temporary<br />

noise<br />

NO<br />

NO<br />

NO<br />

'15 • SRK-T-171<br />

[Broken sensor wire,<br />

connector poor connection]<br />

[Defective fan motor, connector poor<br />

connection, defective indoor PCB]<br />

- 64 -<br />

Correct connection.<br />

Replace sensor.<br />

Correct connector connection<br />

Replace indoor PCB<br />

Replace fan motor (If anomaly<br />

persiste after replacing fan motor,<br />

replace indoor PCB)