Innovativ and efficient - SCHÄFER IT Rack Solutions
Innovativ and efficient - SCHÄFER IT Rack Solutions
Innovativ and efficient - SCHÄFER IT Rack Solutions
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
VI. Electronic components<br />
Power Control, 1 U, power strip with integrated functions<br />
for measuring current, voltage, output, phase angle,<br />
frequency <strong>and</strong> energy<br />
Aluminium profile 1 U, natural anodised, approx. 450 mm in length with<br />
specifications as follows:<br />
n Plastic end face <strong>and</strong> receptacles in grey<br />
n 230 V power supply via the right/lower end face by means of a fixed<br />
HO5VV-F 3G 1,5 mm² 2 m mains cable with angled schuko plug<br />
n With integrated current/output meter<br />
(allowing for phase shift) -> 0–16 A, 3-digit ampere display<br />
n Measuring range from 0.1 – 16 A<br />
n Fully insulated power inputs in acc. with low voltage directive<br />
accuracy class 1<br />
n 8 IEC C 13 sockets, black or<br />
6 Schuko sockets, 35° angled, grey<br />
n With optional locking for C 13<br />
n Delivery includes 2 brackets for mounting the power strip<br />
horizontally/vertically on/in the rack<br />
Type Order no.<br />
6 outlet schuko 7770650<br />
8 outlet IEC C 13 7770660<br />
100<br />
Switchable 24-outlet C 13 power strip, 32 A (SNMP)<br />
n 24 IEC outlets, each with 10 A capacity,<br />
divided into 3 groups of 8 x C 13<br />
n Each group of 8 protected with 16 A fuse<br />
n Overall capacity 32 A<br />
n Connector cable length 2m<br />
n CEE 32 A socket, 3-pole blue, or CEE 16 A 5-pole, red<br />
n Status Led red/green (switch on/switch off ) per port<br />
n Status LED for fuses<br />
n ON delay can be individually set for each port (1 sec. – 30 min.)<br />
n Soft start (after PowerOn, ports switch on gradually with time delay)<br />
n Memory function (after PowerOn, ports will assume on,<br />
off or last status)<br />
n Batch function (each port can be switched off <strong>and</strong><br />
restarted automatically after x seconds)<br />
n Control via Ethernet, HTML <strong>and</strong> script<br />
n All ports can be switched by h<strong>and</strong> on the device itself, also in the<br />
event of power failure<br />
n SNMP 1 <strong>and</strong> 2.c, Syslog functionality<br />
n Password protection for user/admin <strong>and</strong> IP ACLs (firewall)<br />
n Can be updated via Ethernet, also when in operation<br />
(port status remains unchanged)<br />
n Mounting holes in 25 mm pitch pattern<br />
n 1 U, overall length 1500 mm, depth only 60 mm<br />
Type Order no.<br />
Switchable 24-outlet C 13 power strip, 32 A 7771600<br />
3-pole, L/N/PE (SNMP)<br />
Switchable 24-outlet C 13 power strip, 3 x 16 A 7771610<br />
5-pole L1/L2/L3/N/PE (SNMP)