Their high-quality graphite powder coating makes<br />

the tiles electrically conductive.<br />

SWAP PANEL 9 complies with the European test<br />

<strong>and</strong> classification st<strong>and</strong>ard for floor systems<br />

(DIN EN 12825 raised floors <strong>and</strong> DIN EN 13213<br />

hollow floors).<br />

Fitting 9 ventilation tiles enables SWAP PANEL 9<br />

to achieve free clearance of 60 %<br />

Technical Data<br />

Dimensions<br />

Frame dimensions 600 x 600 mm -0,4<br />

height (at the resting points) 35 mm -0,5<br />

height (max. frame height) 80 mm<br />

Tiles dimensions approx. 200 x 200 mm<br />

height 3 mm<br />

Overall height frame + tile (at the resting points) 38 mm<br />

Static load capacity* in acc. with DIN EN 12825<br />

Frame net load (class 6) 10000 N<br />

breaking load ( safety factor 2) > 10000 N<br />

St<strong>and</strong>ard tiles net load (class 4) 4000 N<br />

breaking load ( safety factor 2) > 9000 N<br />

Heavy-duty tiles net load (class 6) 6000 N<br />

breaking load ( safety factor 2) > 12000 N<br />

Ventilation tiles max. load capacity 1000 N<br />

Electrostatics in acc. with DIN EN 1081, DIN VDE 0100 T610<br />

Ground resistance R – procedure B – in acc. with DIN EN 1081 2 R2 < 109 Ω<br />

Contact location resistance R in acc. with DIN VDE 0100 T610 ST RST > 5 x 104 Ω<br />

Dynamic pressure<br />

Max. dynamic pressure 300 PA<br />

Fire protection in acc. with DIN 4102 T1<br />

Carrier plate fire rating A1<br />

* Load applied to centre of the frame <strong>and</strong> the centre of SWAP PANEL 9<br />