n Full integration as a compact unit<br />

n From 4 to 21 kW usable cooling capacity<br />

n 100 % circulating air operation<br />

n Thermally independent of the ambient air<br />

n Parts carrying cooling water in separate housing<br />

With UNIQLE, <strong>SCHÄFER</strong> is systematically implementing the principle of a<br />

cooling system integrated in the server rack. The decision for integration<br />

is a logical step.<br />

Argument 1: Energy efficiency<br />

n Low pressure loss, pump rating correspondingly lower<br />

n Long fan lifetimes as fans are not mounted in heated sections<br />

Argument 2: Space efficiency<br />

Server space is not unlimited! And through the trend to higher <strong>and</strong><br />

higher computer performance accompanied by a greater packing density,<br />

server racks must guarantee a maximum of space efficiency.<br />

This enables the maximum computer density per m² of floor space to<br />

be achieved.<br />

Comparison of floor space<br />

n UNIQLE (integrated cooling system),<br />

floor area in mm (W x H x D): 800 x 2240 x1200<br />

n Server rack of 800 mm width with side cooling solution (300 mm),<br />

floor space in mm (W x H x D): 1100 x 2200 x 1200<br />

Floor space needed for 100 U<br />

n UNIQLE 1.92 m²<br />

n Server rack 3.96 m²<br />

The 5 Elements<br />

n SP54 <strong>Rack</strong><br />

n Cooling System<br />

n <strong>Rack</strong> Control<br />

n Power Management<br />

n Partnership Management<br />

Please note: Pipe work <strong>and</strong> a cold water generator are to be<br />

provided by the customer. Air-intake temperature is regulated<br />

by RMS with integrated control. Operation <strong>and</strong> configuration<br />

via SNMP or http.<br />

Cooling Unit Features<br />

1 cooling unit (self-supporting, insulated housing) installed in lower<br />

section of the UNIQLE unit, consisting of:<br />

n 1 high-capacity heat exchanger<br />

n 1 electrically actuated 3-way valve<br />

n 2 fans (electronically controlled)<br />

n 1 fuse box<br />

Technical features<br />

n Protective housing for heat exchanger<br />

n Maintenance during operation<br />

n Automatic circuit breaker operated from front<br />

Cooling Unit technical data<br />

Operating voltage 230 volts<br />

Power consumption 1.04 kW<br />

Input current 6 A<br />

Spread chilled water 12/18°<br />

Max. air capacity 3500 m²/h<br />

Water throughput rate 2.9 m3 /h<br />

Air supply temperature to server 21° C – 25° C<br />

Dissipated heat approx. 700 Watt (at 21 KW refrigeration<br />

capacity/20° C ambient temperature)<br />

approx. 300 Watt (at 7 KW refrigeration<br />

capacity/23° C ambient temperature)<br />

Water connection for heat exchanger 3/4“ external thread (from below)<br />

Connection for condensate tray 5/8“ hose connection<br />

Pressure loss (water-side) 1 bar max. (inc. 3-way valve)<br />

Operating pressure heat exchanger 10 bar<br />

Coolant water (optional: glycol mixture)<br />