© Siemens <strong>2020</strong><br />

SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />

0.75 kW to 630 kW (1 hp to 700 hp)<br />

SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />

■ Design<br />

Load-side power components<br />

Various load-side power components are available for the<br />

SINAMICS G120X converters. These allow the use of longer<br />

shielded motor cables and increase the motor service life:<br />

• Output reactors for frame sizes FSD to FSJ<br />

Output reactors reduce the rate of voltage rise (dv/dt) and the<br />

height of the current peaks, and can allow longer motor cables<br />

to be connected.<br />

• Sine-wave filters for frame sizes FSA to FSF<br />

Sine-wave filters limit the rate of voltage rise (dv/dt) and the<br />

peak voltages on the motor winding. Similar to an output reactor,<br />

they enable the connection of longer motor cables.<br />

• dv/dt filters plus VPL for frame sizes FSD to FSJ<br />

dv/dt filters plus VPL (Voltage Peak Limiter) limit the voltage<br />

rate-of-rise dv/dt to values of