SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />
0.75 kW to 630 kW (1 hp to 700 hp)<br />
SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />
■ Characteristic curves<br />
Ambient temperature<br />
Frame sizes FSA to FSG:<br />
• Variant PROFINET, EthernNet/IP:<br />
Permissible output current<br />
100<br />
%<br />
90<br />
80<br />
70<br />
92.5<br />
79.25<br />
-20 -10 0 10 20 °C 30 40 45 50 55 60<br />
(-4) (14) (32) (50) (68)(°F)(86)<br />
(104) (122) (140)<br />
Ambient temperature<br />
Permissible output current as a function of ambient temperature for<br />
SINAMICS G120X, frame sizes FSA to FSG, for low overload (LO)<br />
• Variants PROFIBUS DP and USS, Modbus RTU,<br />
BACnet MS/TP:<br />
Permissible<br />
output current<br />
100<br />
%<br />
92.5<br />
90<br />
80<br />
70<br />
66<br />
-20 -10 0 10 20 °C 30 40 45 50 55 60<br />
(-4) (14) (32) (50) (68)(°F)(86)<br />
(104) (122) (140)<br />
Ambient temperature<br />
Permissible output current as a function of ambient temperature for SIN-<br />
AMICS G120X, frame sizes FSA to FSG, for low overload (LO)<br />
G_D011_EN_00572<br />
G_D011_EN_00598<br />
Installation altitude<br />
Frame sizes FSA to FSJ:<br />
Permissible output current<br />
100<br />
%<br />
90<br />
80<br />
70<br />
60<br />
0 1000 2000 3000 m 4000<br />
(3281) (6562) (9843) (ft) (13124)<br />
Installation altitude above sea level<br />
Permissible output current as a function of installation altitude for<br />
SINAMICS G120X for low overload (LO)<br />
The connected motors, power elements and components must<br />
be considered separately.<br />
Permissible line supplies as a function of the installation altitude<br />
• Installation altitude up to 2000 m (6562 ft) above sea level<br />
- Connection to every supply system permitted for the<br />
converter<br />
• Installation altitudes between 2000 m (6562 ft) and 4000 m<br />
(13124 ft) above sea level<br />
- Connection only to a TN system with grounded neutral point<br />
- TN systems with grounded line conductor are not permitted<br />
- The TN line system with grounded neutral point can also be<br />
supplied using an isolation transformer<br />
- The phase-to-phase voltage does not have to be reduced<br />
When using converters on TN systems with voltages 600 V and<br />
at installation altitudes of 2000 m to 4000 m, the TN line supply<br />
must have a grounded neutral point established using an isolation<br />
transformer.<br />
G_D011_EN_00571<br />
2<br />
Frame sizes FSH and FSJ:<br />
Permissible output current<br />
100<br />
%<br />
90<br />
85<br />
80<br />
70<br />
0<br />
(32)<br />
10 20 30<br />
(50) (68) (86)<br />
G_D011_EN_00573<br />
°C 40 45 50 55 60<br />
(°F) (104)(113)(122)<br />
(131)(140)<br />
Ambient temperature<br />
Permissible output current as a function of ambient temperature for<br />
SINAMICS G120X, frame sizes FSH and FSJ, for low overload (LO)<br />
The operating temperature ranges of the operator panels should<br />
be taken into account. The temperature ranges are specified in<br />
the Technical specifications section under Operator panels.<br />
Siemens D 31.5 · March <strong>2020</strong><br />