12.01.2021 Views

motion-control-drives-D31-5-complete-English-2020-03-Update-2020-08

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

© Siemens <strong>2020</strong><br />

SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />

0.75 kW to 630 kW (1 hp to 700 hp)<br />

SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />

■ Technical specifications<br />

6SL32.0-.YE42-.A.0<br />

6SL32.0-.YE42-.U.0<br />

6SL32.0-.YE44-.A.0<br />

6SL32.0-.YE44-.U.0<br />

6SL32.0-.YE46-.A.0<br />

6SL32.0-.YE46-.U.0<br />

6SL32.0-.YE48-.A.0<br />

6SL32.0-.YE48-.U.0<br />

Type of voltage 3AC 3AC 3AC 3AC<br />

Line voltage V 380 ... 480 380 ... 480 380 ... 480 380 ... 480<br />

Output current at line voltage 400 V<br />

• without overload rated value A 149 183 210 256<br />

• with low overload rated value A 145 178 205 250<br />

• with high overload rated value A 110 145 178 205<br />

• maximum A 196 241 277 338<br />

Supplied active power at rated value of<br />

output voltage and at line voltage 400 V<br />

• with low overload kW 75 90 110 132<br />

• with high overload kW 55 75 90 110<br />

Supplied active power [hp] at rated<br />

value of output voltage and at line<br />

voltage 480 V<br />

• with low overload hp 100 125 150 200<br />

• with high overload hp 75 100 125 150<br />

Pulse frequency kHz 4 4 4 4<br />

Efficiency 0.98 0.98 0.98 0.98<br />

Power loss maximum 1) kW 1.23 1.57 1.83 2.35<br />

Cooling air flow<br />

m³/s 0.153 (19451.32021) 0.153 (19451.32021) 0.153 (19451.32021) 0.153 (19451.32021)<br />

(ft³/h)<br />

1 m measuring surface sound pressure dB 72 72 72 72<br />

level maximum<br />

Input current at line voltage 400 V<br />

• with low overload rated value A 140 172 198 242<br />

• with high overload rated value A 117 154 189 218<br />

for mains supply line<br />

• Type of electrical connection M10 screw M10 screw M10 screw M10 screw<br />

• Number of connections 2 2 2 2<br />

• Connectable conductor cross-section mm² 35 ... 120 35 ... 120 35 ... 120 35 ... 120<br />

• Connectable conductor cross-section 2 ... -3 2...-3 2...-3 2 ... -3<br />

(AWG)<br />

for motor supply line<br />

• Type of electrical connection M10 screw M10 screw M10 screw M10 screw<br />

• Number of connections 2 2 2 2<br />

• Connectable conductor cross-section mm² 35 ... 120 35 ... 120 35 ... 120 35 ... 120<br />

• Connectable conductor cross-section 2 ... -3 2...-3 2...-3 2 ... -3<br />

(AWG)<br />

Type of electrical connection for PE<br />

M10 screw M10 screw M10 screw M10 screw<br />

conductor<br />

Cable length for motor<br />

• shielded maximum 2) m(ft) 300 (984.25197) 300 (984.25197) 300 (984.25197) 300 (984.25197)<br />

• unshielded maximum 2) m(ft) 450 (1476.37795) 450 (1476.37795) 450 (1476.37795) 450 (1476.37795)<br />

Dimensions<br />

•Width mm (in) 305 (12.00787) 305 (12.00787) 305 (12.00787) 305 (12.00787)<br />

•Height mm (in) 709 (27.91339) 709 (27.91339) 709 (27.91339) 709 (27.91339)<br />

•Depth mm (in) 360 (14.17323) 360 (14.17323) 360 (14.17323) 360 (14.17323)<br />

Frame size FSF FSF FSF FSF<br />

Weight, approx. 3) kg (lb) 61 (134.48182) 61 (134.48182) 67 (147.70954) 67 (147.70954)<br />

2<br />

1) Typical values. More information can be found on the Internet at<br />

https://support.industry.siemens.com/cs/document/94059311<br />

2) The values apply without compliance to the EMC category.<br />

For more information, see Maximum permissible motor cable lengths<br />

SINAMICS G120X and on the Internet at<br />

www.siemens.com/sinamics-g120x/documentation<br />

3) The values apply for converters without integrated line filter.<br />

For more information, see on the Internet at<br />

www.siemens.com/sinamics-g120x/documentation<br />

<strong>Update</strong> <strong>08</strong>/<strong>2020</strong><br />

Siemens D 31.5 · March <strong>2020</strong><br />

2/37