© Siemens <strong>2020</strong><br />
SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />
0.75 kW to 630 kW (1 hp to 700 hp)<br />
SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />
2<br />
■ Technical specifications<br />
6SL32.0-.YH50-.C.0 6SL32.0-.YH52-.C.0 6SL32.0-.YH54-.C.0 6SL3220-.YH56-.C.0 6SL3220-.YH58-.C.0<br />
Type of voltage 3AC 3AC 3AC 3AC 3AC<br />
Line voltage V 500 ... 690 500 ... 690 500 ... 690 500 ... 690 500 ... 690<br />
Output current at line voltage 690 V<br />
• without overload rated value A 175 213 256 368 400<br />
• with low overload rated value A 171 2<strong>08</strong> 250 330 385<br />
• with high overload rated value A 144 171 2<strong>08</strong> 272 314<br />
• maximum A 231 281 338 487 529<br />
Supplied active power at rated value of<br />
output voltage and at line voltage 690 V<br />
• with low overload kW 160 200 250 315 355<br />
• with high overload kW 132 160 200 250 315<br />
Supplied active power [hp] at rated<br />
value of output voltage and at line<br />
voltage 600 V<br />
• with low overload hp 150 200 250 350 400<br />
• with high overload hp 150 150 200 250 350<br />
Pulse frequency kHz 2 2 2 2 2<br />
Efficiency 0.98 0.98 0.98 0.98 0.98<br />
Power loss maximum 1) kW 2.94 3.7 4.64 5.402 6.191<br />
Cooling air flow<br />
m³/s 0.21 (26697.89049) 0.21 (26697.89049) 0.21 (26697.89049) 0.362 (46022.07788) 0.362 (46022.07788)<br />
(ft³/h)<br />
1 m measuring surface sound pressure dB 74 74 74 74 74<br />
level maximum<br />
Input current at line voltage 690 V<br />
• with low overload rated value A 175 210 255 343 401<br />
• with high overload rated value A 160 185 225 283 327<br />
for mains supply line<br />
• Type of electrical connection M10 screw M10 screw M10 screw M12 screw M12 screw<br />
• Number of connections 2 2 2 4 4<br />
• Connectable conductor cross-section mm² 35 ... 185 35 ... 185 35 ... 185 35 ... 240 35 ... 240<br />
• Connectable conductor cross-section 2 ... -3 2...-3 2...-3 2...-3 2...-3<br />
(AWG)<br />
for motor supply line<br />
• Type of electrical connection M10 screw M10 screw M10 screw M12 screw M12 screw<br />
• Number of connections 2 2 2 4 4<br />
• Connectable conductor cross-section mm² 35 ... 185 35 ... 185 35 ... 185 35 ... 240 35 ... 240<br />
• Connectable conductor cross-section 2 ... -3 2...-3 2...-3 2...-3 2...-3<br />
(AWG)<br />
Type of electrical connection for PE<br />
M10 screw M10 screw M10 screw M12 screw M12 screw<br />
conductor<br />
Cable length for motor<br />
• shielded maximum 2) m(ft) 150 (492.12598) 150 (492.12598) 150 (492.12598) 150 (492.12598) 150 (492.12598)<br />
Dimensions<br />
•Width mm (in) 305 (12.00787) 305 (12.00787) 305 (12.00787) 548 (21.5748) 548 (21.5748)<br />
•Height mm (in) 999 (39.33071) 999 (39.33071) 999 (39.33071) 1695 (66.73228) 1695 (66.73228)<br />
•Depth mm (in) 360 (14.17323) 360 (14.17323) 360 (14.17323) 393 (15.47244) 393 (15.47244)<br />
Frame size FSG FSG FSG FSH FSH<br />
Weight, approx. kg (lb) 105 (231.48536) 113 (249.12234) 120 (264.5547) 158 (348.33<strong>03</strong>5) 158 (348.33<strong>03</strong>5)<br />
1) Typical values. More information can be found on the Internet at<br />
https://support.industry.siemens.com/cs/document/94059311<br />
2/44 Siemens D 31.5 · March <strong>2020</strong><br />
<strong>Update</strong> <strong>08</strong>/<strong>2020</strong><br />
2) The values apply with compliance to the EMC category.<br />
For more information, see Maximum permissible motor cable lengths<br />
SINAMICS G120X and on the Internet at<br />
www.siemens.com/sinamics-g120x/documentation