© Siemens <strong>2020</strong><br />
SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />
0.75 kW to 630 kW (1 hp to 700 hp)<br />
SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />
2<br />
■ Technical specifications<br />
6SL32.0-.YE18-.A.0<br />
6SL32.0-.YE18-.U.0<br />
6SL32.0-.YE20-.A.0<br />
6SL32.0-.YE20-.U.0<br />
6SL32.0-.YE22-.A.0<br />
6SL32.0-.YE22-.U.0<br />
6SL32.0-.YE24-.A.0<br />
6SL32.0-.YE24-.U.0<br />
Type of voltage 3AC 3AC 3AC 3AC<br />
Line voltage V 380 ... 480 380 ... 480 380 ... 480 380 ... 480<br />
Output current at line voltage 400 V<br />
• without overload rated value A 8 10.5 13.6 18.5<br />
• with low overload rated value A 7.7 10.2 13.2 18<br />
• with high overload rated value A 5.9 7.7 10.2 13.2<br />
• maximum A 9.1 14 18 24<br />
Supplied active power at rated value of<br />
output voltage and at line voltage 400 V<br />
• with low overload kW 3 4 5.5 7.5<br />
• with high overload kW 2.2 3 4 5.5<br />
Supplied active power [hp] at rated<br />
value of output voltage and at line<br />
voltage 480 V<br />
• with low overload hp 4 5 7.5 10<br />
• with high overload hp 3 4 5 7.5<br />
Pulse frequency kHz 4 4 4 4<br />
Efficiency 0.98 0.98 0.98 0.98<br />
Power loss maximum 1) kW 0.126 0.138 0.181 0.245<br />
Cooling air flow<br />
m³/s 0.005 (635.66406) 0.005 (635.66406) 0.0092 (1169.62187) 0.0092 (1169.62187)<br />
(ft³/h)<br />
1 m measuring surface sound pressure dB 55 63 63 63<br />
level maximum<br />
Input current at line voltage 400 V<br />
• with low overload rated value A 6.9 9.75 12 17<br />
• with high overload rated value A 5.29 7.36 9.27 12.47<br />
for mains supply line<br />
• Type of electrical connection Screw-type terminals Screw-type terminals Screw-type terminals Screw-type terminals<br />
• Number of connections 1 1 1 1<br />
• Connectable conductor cross-section mm² 1.5 ... 2.5 6...16 6...16 6 ... 16<br />
• Connectable conductor cross-section 18 ... 14 10 ... 6 10 ... 6 10 ... 6<br />
(AWG)<br />
for motor supply line<br />
• Type of electrical connection Screw-type terminals Screw-type terminals Screw-type terminals Screw-type terminals<br />
• Number of connections 1 1 1 1<br />
• Connectable conductor cross-section mm² 1.5 ... 2.5 6...16 6...16 6 ... 16<br />
• Connectable conductor cross-section<br />
(AWG)<br />
18 ... 14 10 ... 6 10 ... 6 10 ... 6<br />
Type of electrical connection for PE<br />
conductor<br />
Cable length for motor<br />
On housing with<br />
M4 screw<br />
On housing with<br />
M4 screw<br />
On housing with<br />
M4 screw<br />
On housing with<br />
M4 screw<br />
• shielded maximum 2) m(ft) 150 (492.12598) 150 (492.12598) 150 (492.12598) 150 (492.12598)<br />
• unshielded maximum 2) m(ft) 300 (984.25197) 300 (984.25197) 300 (984.25197) 300 (984.25197)<br />
Dimensions<br />
•Width mm (in) 73 (2.87402) 100 (3.93701) 100 (3.93701) 100 (3.93701)<br />
•Height mm (in) 232 (9.13386) 275 (10.82677) 275 (10.82677) 275 (10.82677)<br />
•Depth mm (in) 209 (8.22835) 209 (8.22835) 209 (8.22835) 209 (8.22835)<br />
Frame size FSA FSB FSB FSB<br />
Weight, approx. 3) kg (lb) 3.2 (7.05478) 5.83 (12.85293) 5.83 (12.85293) 5.83 (12.85293)<br />
1) Typical values. More information can be found on the Internet at<br />
https://support.industry.siemens.com/cs/document/94059311<br />
2) The values apply without compliance to the EMC category.<br />
For more information, see Maximum permissible motor cable lengths<br />
SINAMICS G120X and on the Internet at<br />
www.siemens.com/sinamics-g120x/documentation<br />
3) The values apply for converters without integrated line filter.<br />
For more information, see on the Internet at<br />
www.siemens.com/sinamics-g120x/documentation<br />
2/34 Siemens D 31.5 · March <strong>2020</strong><br />
<strong>Update</strong> <strong>08</strong>/<strong>2020</strong>