© Siemens <strong>2020</strong><br />

SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />

0.75 kW to 630 kW (1 hp to 700 hp)<br />

SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />

■ Characteristic curves<br />

System operating voltage<br />

200 V converters frame sizes FSA to FSF:<br />

400 V converters frame sizes FSH and FSJ:<br />

110<br />

%<br />

2<br />

Output current<br />

105<br />

100<br />

95<br />

90<br />

85<br />

200 210 220 230 240<br />

V<br />

Input voltage<br />

G_D011_EN_00610<br />

Output current<br />

100<br />

%<br />

95<br />

90<br />

85<br />

80<br />

75<br />

360 380 400 420 440 460 480 V 500<br />

Input voltage<br />

G_D011_EN_00576<br />

Permissible output current as a function of the input voltage for<br />

200-V-SINAMICS G120X converters frame sizes FSA to FSF<br />

400 V converters frame sizes FSA to FSG:<br />

Output power<br />

110<br />

%<br />

105<br />

100<br />

95<br />

90<br />

85<br />

300 380 390 400 415 V 528<br />

Input voltage<br />

Permissible output power as a function of the input voltage for<br />

400-V-SINAMICS G120X converters frame sizes FSA to FSG at 100%<br />

output current in the range of 380 V to 415 V<br />

(the temperature protection of the converter can reduce the current or<br />

pulse frequency above 415 V)<br />

Output power<br />

110<br />

%<br />

105<br />

100<br />

95<br />

90<br />

85<br />

440 450 460 470 480 V 528<br />

Input voltage<br />

Permissible output power as a function of the input voltage for<br />

400-V-SINAMICS G120X converters frame sizes FSA to FSG at 100%<br />

output current in the range of 440 V to 480 V<br />

(the temperature protection of the converter can reduce the current or<br />

pulse frequency above 480 V)<br />

Further information is available in the manual on the Internet at:<br />

www.siemens.com/sinamics-g120x/documentation<br />

G_D011_EN_00612<br />

G_D011_EN_00611<br />

Permissible output current as a function of input voltage for 400 V<br />

SINAMICS G120X converters, frame sizes FSH and FSJ, for low overload<br />

(LO)<br />

600 V converters frame sizes FSA to FSG:<br />

Output power<br />

100<br />

%<br />

95<br />

90<br />

85<br />

80<br />

75<br />

72<br />

70<br />

500 510 530 550 570 590 610 630 650 670 V 690<br />

Input voltage<br />

Permissible output power as a function of input voltage for<br />

600-V-SINAMICS G120X converters frame sizes FSA to FSG at 100%<br />

output current in the range of 500 V to 690 V<br />

Further information is available in the manual on the Internet at:<br />

www.siemens.com/sinamics-g120x/documentation<br />

600 V converters frame sizes FSH and FSJ:<br />

Output current<br />

100<br />

%<br />

95<br />

91<br />

85<br />

80<br />

75<br />

70<br />

480 500 520 540 560 580 600 620 640 660 V 690<br />

Input voltage<br />

Permissible output current as a function of input voltage for 600 V<br />

SINAMICS G120X converters, frame sizes FSH and FSJ, for low<br />

overload (LO)<br />

G_D011_EN_00613<br />

G_D011_EN_00578<br />

2/50 Siemens D 31.5 · March <strong>2020</strong><br />

<strong>Update</strong> <strong>08</strong>/<strong>2020</strong>