motion-control-drives-D31-5-complete-English-2020-03-Update-2020-08
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
© Siemens <strong>2020</strong><br />
SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater<br />
0.75 kW to 630 kW (1 hp to 700 hp)<br />
Supplementary system components > SINAMICS G120X I/O Extension Module<br />
2<br />
■ Overview<br />
SINAMICS G120X I/O Extension Module<br />
The SINAMICS G120X I/O Extension Module increases the number<br />
of I/O terminals of the converter and therefore allows for<br />
additional converter <strong>control</strong> functionalities. It also allows for the<br />
connection to an operator panel or the SINAMICS G120 Smart<br />
Access.<br />
The optional SINAMICS G120X I/O Extension Module has 2 DI,<br />
2 AO, 4 DO (relay), and up to 2 Pt1000/Ni1000 temperature<br />
sensors can be directly connected.<br />
Notes:<br />
The SINAMICS G120X I/O Extension Module is only supported<br />
for SINAMICS G120X converters with FS codes 02 02 (FSA to<br />
FSG) / 02 (FSH and FSJ) and firmware V1.01.<br />
The FS code can be found on the rating plate of the converter.<br />
■ Selection and ordering data<br />
Description<br />
SINAMICS G120X I/O Extension<br />
Module<br />
for the direct connection of<br />
Pt1000/Ni1000 temperature sensors<br />
NEW NEU<br />
Article No.<br />
6SL3255-0BE00-0AA0<br />
■ More information<br />
Further information and documentation is available on the<br />
Internet at:<br />
www.siemens.com/sinamics-g120x/documentation<br />
■ Technical specifications<br />
Article No.<br />
6SL3255-0BE00-0AA0<br />
Analog inputs<br />
Number of analog inputs 2<br />
Design of the sensor to detect the<br />
ambient temperature connectable<br />
Connectable conductor cross-section at<br />
the analog input<br />
AWG number as coded connectable<br />
conductor cross-section at the analog<br />
input<br />
Input current<br />
Analog outputs<br />
2 analog inputs for connecting temperature<br />
sensors Pt1000/Ni1000.<br />
One of them can be used as an<br />
analog input.<br />
0.5 ... 1.5 mm²<br />
21 ... 16<br />
0...20mA<br />
Number of analog outputs 2<br />
Analog outputs Type<br />
Non-isolated output<br />
Connectable conductor cross-section at 0.5 ... 1.5 mm²<br />
the analog output<br />
AWG number as coded connectable 21 ... 16<br />
conductor cross-section at the analog<br />
output<br />
Output voltage at analog output 0...10V<br />
Output current at analog output 0...20mA<br />
Digital inputs<br />
Number of digital inputs 2<br />
Connectable conductor cross-section at 0.5 ... 1.5 mm²<br />
the digital inputs<br />
AWG number as coded connectable 21 ... 16<br />
conductor cross-section at the digital<br />
inputs<br />
Digital inputs Input voltage for signal<br />
"0" "1"<br />
Digital inputs Input voltage for signal<br />
"1" "0"<br />
Input voltage at digital input maximum<br />
Digital outputs<br />
11 V<br />
5V<br />
30 V<br />
Number of digital outputs 4<br />
Connectable conductor cross-section at 1.5 mm²<br />
the digital outputs maximum<br />
AWG number as coded connectable 16<br />
conductor cross section at the digital<br />
outputs maximum<br />
Output current at digital output<br />
Mechanical data<br />
Width<br />
Depth<br />
Height<br />
2A<br />
71 mm<br />
27 mm<br />
117 mm<br />
2/60 Siemens D 31.5 · March <strong>2020</strong><br />