4.5.5 Current signals ((0)4-20 mA)<br />

A current signal like (0)4-20 mA is less sensitive to<br />

disturbances than a 0-10 V signal, because it is connected to<br />

an input which has a lower impedance (250 �) than a<br />

voltage signal (20 k�). It is therefore strongly advised to use<br />

current control signals if the cables are longer than a few<br />

metres.<br />

4.5.6 Twisted cables<br />

Analogue and digital signals are less sensitive to interference<br />

if the cables carrying them are “twisted”. This is certainly to<br />

be recommended if screening cannot be used. By twisting<br />

the wires the exposed areas are minimised. This means that<br />

in the current circuit for any possible High Frequency (HF)<br />

interference fields, no voltage can be induced. For a PLC it<br />

is therefore important that the return wire remains in<br />

proximity to the signal wire. It is important that the pair of<br />

wires is fully twisted over 360°.<br />

4.6 Connecting options<br />

The option cards are connected by the optional connectors<br />

X4 or X5 on the control board see Fig. 28, page 27 and<br />

mounted above the control board. The inputs and outputs<br />

of the option cards are connected in the same way as other<br />

control signals.<br />

32 Control Connections CG Drives & Automation, 01-5325-01r1