7.6.2 Fixed MASTER<br />
This is the default setting of the Pump Control. The AC<br />
drive controls the Master pump which is always running.<br />
The relay outputs start and stop the other pumps P1 to P6,<br />
depending on flow/pressure. In this configuration a maximum<br />
of 7 pumps can be controlled, see Fig. 43. To equalize<br />
the lifetime of the additional pumps it is possible to select<br />
the pumps depending on the run time history of each pump.<br />
R:SlavePump6<br />
R:SlavePump5<br />
FDU R:SlavePump4<br />
MASTER R:SlavePump3<br />
R:SlavePump2<br />
R:SlavePump1<br />
(NG_50-PC-4_1)<br />
PM<br />
See menu:<br />
[393] Select Drive<br />
[39H] to [39N] Run Time 1 - 6, Pump<br />
[554] to [55C] Relays<br />
Fig. 48 Fixed MASTER control<br />
P1 P2 P3 P4 P5 P6<br />
NOTE: The pumps MAY have different powers, however<br />
the MASTER pump MUST always be the largest.<br />
7.6.3 Alternating MASTER<br />
With this function the Master pump is not fixed to the AC<br />
drive all the time. After the AC drive is powered up or<br />
started again after a stop or sleep mode the Master pump is<br />
selected via the relay set to function Master Pump. section<br />
7.6.7 on page 44 shows a detailed wiring diagram with 3<br />
pumps. The purpose of this function is that all pumps are<br />
used equally, so the lifetime of all pumps, including the<br />
Master pump, will be equalized. Maximum 6 pumps can be<br />
controlled with this function.<br />
Fig. 49 Alternating MASTER Control<br />
P1 P2 P3 P4 P5 P6<br />
NOTE: The pumps MUST have all the same power.<br />
48 Main Features CG Drives & Automation, 01--5325-01r1<br />
FDU<br />
MASTER<br />
(NG_50-PC-5_1)<br />
R: SlavePump6<br />
R: SlavePump5<br />
R: SlavePump4<br />
R: SlavePump3<br />
R: SlavePump2<br />
R: SlavePump1<br />
R: MasterPump6<br />
R: MasterPump5<br />
R: MasterPump4<br />
R: MasterPump3<br />
R: MasterPump2<br />
R: MasterPump1<br />
See menu:<br />
[393] to [396]<br />
[553] to [55C]