3 Error display : e1 [Communication error between remote controller~Indoor unit]<br />

Red LED<br />

Green LED<br />

Indoor unit<br />

Stays OFF<br />

Keeps flashing<br />

Voltage<br />

between X and Z<br />

approximately<br />

10~11 V?<br />

NO<br />

Voltage<br />

fluctuates between<br />

5~11 V between<br />

Y and Z.<br />

YES<br />

Voltage<br />

fluctuates between<br />

5~10 V between<br />

Y and Z<br />

indoors.<br />

YES<br />

Voltage<br />

fluctuates between<br />

5~10 V between<br />

CNB Y and Z.<br />

YES<br />

Indoor unit<br />

resets every ❇<br />

4 minutes.<br />

YES<br />

YES<br />

NO<br />

NO<br />

NO<br />

NO<br />

Red LED<br />

Green LED<br />

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.<br />

Red LED<br />

Green LED<br />

Power supply reset<br />

Normal?<br />

NO<br />

Replacement indoor<br />

unit control PCB<br />

Indoor unit<br />

Stays OFF<br />

Stays OFF or Lights<br />

continuously<br />

Replacement remote<br />

controller<br />

Remote controller<br />

wire disconnection<br />

Terminal block CNB<br />

harness is defective.<br />

Outdoor unit<br />

Stays OFF<br />

Keeps flashing<br />

❇ After the green LED lights up once,<br />

it begins flashing again continuously.<br />

The louver moves once in the<br />

close direction.<br />

YES<br />

Power supply reset<br />

Red LED<br />

Noise<br />

Green LED<br />

Power supply OFF<br />

Outdoor unit<br />

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.<br />

● Only case of FDT<br />

Stays OFF<br />

Is the voltage<br />

between CNW8<br />

2-3 12V?<br />

Lighting YES<br />

Power supply reset<br />

Normal<br />

YES<br />

NO<br />

NO<br />

The unit is normal.<br />

(The malfunction is due to noise, etc.)<br />

Check the CNW5-<br />

CNW8 harness.<br />

Replacement indoor<br />

unit control PCB<br />

- 15 -<br />

Stays OFF<br />

YES<br />

Keeps flashing<br />

Power supply<br />

reset<br />

Normal?<br />

Is the<br />

resistance between<br />

Y~Z on the remote controller<br />

approximately<br />

10kΩ?<br />

NO<br />

Replacement remote<br />

controller<br />

● Cases of other than FDT<br />

Remote controller<br />

wire is removed<br />

Resistance is<br />

approximately 10kΩ<br />

between indoor<br />

Y~Z.<br />

YES<br />

Remote controller<br />

wire short circuit<br />

YES<br />

NO<br />

NO<br />

Disconnection ?<br />

Noise?<br />

NO<br />

Is the<br />

voltage at the transfomer's<br />

secondary side (red-red) 15V<br />

or higher?<br />

YES<br />

Replacement indoor unit<br />

power supply PCB<br />

Is it normalized?<br />

NO<br />

Defective indoor unit control PCB<br />

Replace. (Defective CPU)<br />

YES<br />

Replacement<br />

remote controller<br />

Replacement indoor<br />

unit control PCB<br />

YES<br />

NO<br />

Harness<br />

exchange<br />

Transformer<br />

exchange<br />

Unit is normal.<br />

(Runaway of indoor<br />

unit CPU due to<br />

noise, etc.<br />

Transient trouble)