S Only case of FDKN<br />

Only case of 151~251 types<br />

CNM<br />

1 and 3 (Red – Black)<br />

DC280V?<br />

CNM<br />

4 and 3 (White-Black)<br />

DC15V?<br />

YES<br />

Does the<br />

fan motor turn<br />

smoothly by<br />

hand?<br />

YES<br />

NO<br />

NO<br />

YES YES<br />

NO<br />

NO<br />

Replacement indoor<br />

unit control PCB<br />

Secondary<br />

side of transformer<br />

(red-red) 14V<br />

or more<br />

(2)<br />

Is the voltage<br />

at CNM 5 (Yellow) DC 1V<br />

YES<br />

or higher?<br />

Note (2) CNM 3 (Black) is GND.<br />

Replacement indoor<br />

unit control PCB<br />

Only case of 301 type<br />

CNM<br />

1 and 4 (Red-Blue)<br />

DC 0~60V ?<br />

NO<br />

Turn the power off and wait<br />

a short time (30 min. ~ 1 hr.)<br />

YES<br />

When tried again,<br />

the fan goes ON.<br />

YES<br />

Replacement indoor<br />

unit control PCB<br />

3 (Black) is GND.<br />

3 (Black) is GND.<br />

3 (black) is GND.<br />

YES<br />

YES<br />

NO<br />

Replacement transformer<br />

Detective fan motor<br />

Replacement fan<br />

motor<br />

Check the<br />

circumstances.<br />

- 19 -<br />

NO<br />

NO<br />

Abnormal data check<br />

with remote controller<br />

After check reset,<br />

fan runs on Me.<br />

Fan ON?<br />

YES<br />

Was it reproduced?<br />

YES<br />

YES<br />

NO<br />

Check the<br />

circumstances.<br />

When the (1)<br />

motor is turning, does<br />

the voltage at CNM 6 (Blue)<br />

fluctuate between<br />

DC 0 ~ 15 V?<br />

Note (1) CNM 3 (Black) is GND.<br />

Replacement indoor<br />

unit control PCB<br />

● Display conditions<br />

If an indoor unit fan motor’s speed is detected to be less than<br />

200 rpm continuously for 30 seconds, the fan motor stops for 2<br />

seconds. After 2 seconds, it starts again, but this occurs 4 times<br />

within a period of 1 hour.<br />

NO<br />

NO<br />

After check reset,<br />

fan runs on Me.<br />

Fan ON ?<br />

YES<br />

Was it reproduced?<br />

YES<br />

When (1)<br />

the motor is turning,<br />

does the voltage at CNM 5<br />

(White) fluctuate between<br />

DC 0 ~ 15 V?<br />

YES<br />

Replacement indoor<br />

unit control PCB<br />

NO<br />

NO<br />

Check the<br />

circumstances.<br />

Replacement fan<br />

motor<br />

Note (1) CNM 4 (Blue) is GND.<br />

● Display conditions<br />

If an indoor unit fan motor’s speed is detected to be less than<br />

200 rpm continuously for 30 seconds, the fan motor stops for 2<br />

seconds. After 2 seconds, it starts again, but this occurs 4 times<br />

within a period of 1 hour.