1 Error display : e5 [Communications error during operation]<br />

Indoor unit<br />

Outdoor unit<br />

Red LED<br />

2 time flash Red LED<br />

2 time flash<br />

Green LED Keeps flashing Green LED Keeps flashing<br />

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.<br />

Is the connection<br />

of the signal wires at the<br />

outdoor unit poor?<br />

YES<br />

(1) (2)<br />

NO<br />

Is the connection<br />

of the signal wires at the<br />

indoor unit poor?<br />

Repair Repair<br />

NO Reset power<br />

Did the remote “ WAIT ” “ WAIT ”<br />

controller’s LCD return<br />

supply.<br />

to normal?<br />

Go to display diagnosis (page 140).<br />

YES YES<br />

The unit is normal.<br />

Malfunction was due to<br />

transient noise, etc.<br />

Notes (1) Check for poor connections (disconnection, looseness) on the outdoor unit’s terminal block.<br />

(2) Check for poor connections or disconnection of the signal lines between the indoor and outdoor units.<br />

Red LED<br />

Green LED<br />

Indoor unit<br />

2 time flash<br />

Keeps flashing<br />

Red LED<br />

Outdoor unit<br />

Stays OFF<br />

Green LED Keeps flashing<br />

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.<br />

Reset power supply. Did it return to normal?<br />

NO<br />

Outdoor unit’s control PCB is<br />

faulty. (Network communications<br />

circuit is faulty.) Replace<br />

- 25 -<br />

YES<br />

Malfunction is due to noise, etc.<br />

(The outdoor unit’s CPU went<br />

out of control due to noise during<br />

power on.)<br />

2 Error display : e32 [Power supply phases reversed] [Only case of 301~601 type]<br />

Red LED<br />

Green LED<br />

Indoor unit<br />

Stays OFF<br />

Keeps flashing<br />

Are the power supply<br />

phases reversed?<br />

NO<br />

Are the connections<br />

to the reverse phase detection<br />

circuit lines correct?<br />

YES<br />

YES<br />

NO<br />

Outdoor unit’s control PCB is faulty.<br />

Replace<br />

(Reverse phase detection circuit is faulty.)<br />

Red LED<br />

Outdoor unit<br />

1 time flash<br />

Green LED Keeps flashing<br />

Repair<br />

Repair