6 Error display : e8 [Heating overload]<br />

Indoor unit<br />

Outdoor unit<br />

Red LED<br />

1 time flash Red LED<br />

Stays OFF<br />

Green LED Keeps flashing Green LED Keeps flashing<br />

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.<br />

Is the air filter clogged?<br />

NO<br />

Are the connections to<br />

the indoor heat exchanger thermistor<br />

OK?<br />

Repair<br />

NO<br />

7 Error display : e9 [Drain trouble]<br />

Indoor unit<br />

Outdoor unit<br />

Red LED<br />

1 time flash Red LED<br />

Stays OFF<br />

Green LED Keeps flashing Green LED Keeps flashing<br />

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.<br />

Abnormal data check<br />

in remote controller<br />

Is there any<br />

overflow?<br />

YES<br />

Drain motor ON from<br />

remote controller.<br />

DM<br />

operation<br />

YES<br />

Is drain<br />

piping unclogged?<br />

Is the slop OK?<br />

YES<br />

DM check<br />

YES<br />

YES<br />

● Abnormal Temperature Detection<br />

Abnormal stop<br />

Heating is<br />

possible.<br />

56 63<br />

Indoor unit heat exchanger temp. (˚C)<br />

NO<br />

Are the characteristics of<br />

the indoor heat exchanger thermistor<br />

OK?<br />

NO<br />

NO<br />

Clean it.<br />

NO<br />

Defective indoor unit heat<br />

exchanger thermistor<br />

Replacement<br />

DC 12 V<br />

at both terminals<br />

of CNI?<br />

YES<br />

Float switch check<br />

Correction<br />

- 17 -<br />

NO<br />

Notes (1) Check if the overload state exists or not using the following check points.<br />

Is there a short circuit?<br />

Is the indoor heat exchanger dirty or clogged?<br />

Is the outdoor unit’s fan control normal?<br />

Is the indoor or outdoor air temperature too high?<br />

(2) See the figure page 142 for indoor heat exchanger thermistor characteristics.<br />

YES<br />

((<br />

Check the remote controller for abnormal data.<br />

Does the heating<br />

overload state exist?<br />

Replacement indoor<br />

unit PCB<br />

AC 220/240 V<br />

at both terminals<br />

of CNR?<br />

YES<br />

DM check of<br />

motor wiring<br />

NO<br />

Check the cooling system.<br />

NO<br />

YES<br />

Replacement indoor<br />

unit control PCB<br />

Adjust<br />

● Display condition<br />

An abnormal stop occurs if this state is detected 5 times within 60 minutes of the<br />

first detection, or if the overload state is detected continuously for 6 minutes.