Structural <strong>Fire</strong>proofing<br />
Beam<br />
2 Hour <strong>Fire</strong>-Rated Construction Reference<br />
Construction Detail Description Test Number Comments Index<br />
3 Hour <strong>Fire</strong>-Rated Construction<br />
3 7 ⁄8"<br />
4"<br />
2 3 ⁄4"<br />
2 3 ⁄4"<br />
4"<br />
4 1 ⁄8"<br />
4 Hour <strong>Fire</strong>-Rated Construction<br />
1 7 ⁄8" 1 7 ⁄8"<br />
• 5/8" Sheetrock <strong>Fire</strong>code Core gypsum UL Des N501, Structural member tested: E-25<br />
panels N502 W8 x 24 (beam only)<br />
– 1-5/8" steel run channel brackets 24" o.c.<br />
– 1-3/8" x 7/8" corner angles attached to channel<br />
brackets<br />
– joints finished<br />
– 2-1/2" concrete deck on fluted steel floor<br />
• optional veneer plaster<br />
– 1-5/8" steel run channel brackets 24" o.c. UL Des N505 Structural member tested: E-26<br />
– 7/8" x 1-3/8" corner angles attached to brackets W8 x 24 (beam only)<br />
• 5/8" Sheetrock <strong>Fire</strong>code Core gypsum <strong>Fire</strong> rating for restrained assembly; 2 hour<br />
panels rating for unrestrained assembly<br />
– 1" 20 gauge hex mesh on bottom over middle<br />
layer<br />
– joints finished<br />
– 2-1/2" concrete deck on fluted steel floor<br />
– 1-5/8" steel run channel brackets 24" o.c. UL Des N505 Structural member tested: E-27<br />
– 1/8" x 1-3/8" corner angles attached to W8 x 24 (beam only)<br />
channel brackets<br />
• 5/8" imperial <strong>Fire</strong>code Core gypsum<br />
Base<br />
– 1" 20 gauge hex mesh on bottom<br />
over middle layer<br />
– metal beads on corners<br />
– joints taped<br />
• 1/16" veneer plaster finish<br />
– 2-1/2" concrete deck on fluted steel floor<br />
– 3.4 lb self-furring diamond mesh metal lath UL Des D403 Structural member tested: E-28<br />
enclosing beam W12 x 58<br />
• 1-1/2" 100:2 gypsum-perlite plaster Suitable for protection of beams and girders<br />
56 <strong>USG</strong> <strong>Fire</strong>-<strong>Resistant</strong> <strong>Assemblies</strong>