E<br />

Structural <strong>Fire</strong>proofing<br />

Beam<br />

2 Hour <strong>Fire</strong>-Rated Construction Reference<br />

Construction Detail Description Test Number Comments Index<br />

3 Hour <strong>Fire</strong>-Rated Construction<br />

3 7 ⁄8"<br />

4"<br />

2 3 ⁄4"<br />

2 3 ⁄4"<br />

4"<br />

4 1 ⁄8"<br />

4 Hour <strong>Fire</strong>-Rated Construction<br />

1 7 ⁄8" 1 7 ⁄8"<br />

• 5/8" Sheetrock <strong>Fire</strong>code Core gypsum UL Des N501, Structural member tested: E-25<br />

panels N502 W8 x 24 (beam only)<br />

– 1-5/8" steel run channel brackets 24" o.c.<br />

– 1-3/8" x 7/8" corner angles attached to channel<br />

brackets<br />

– joints finished<br />

– 2-1/2" concrete deck on fluted steel floor<br />

• optional veneer plaster<br />

– 1-5/8" steel run channel brackets 24" o.c. UL Des N505 Structural member tested: E-26<br />

– 7/8" x 1-3/8" corner angles attached to brackets W8 x 24 (beam only)<br />

• 5/8" Sheetrock <strong>Fire</strong>code Core gypsum <strong>Fire</strong> rating for restrained assembly; 2 hour<br />

panels rating for unrestrained assembly<br />

– 1" 20 gauge hex mesh on bottom over middle<br />

layer<br />

– joints finished<br />

– 2-1/2" concrete deck on fluted steel floor<br />

– 1-5/8" steel run channel brackets 24" o.c. UL Des N505 Structural member tested: E-27<br />

– 1/8" x 1-3/8" corner angles attached to W8 x 24 (beam only)<br />

channel brackets<br />

• 5/8" imperial <strong>Fire</strong>code Core gypsum<br />

Base<br />

– 1" 20 gauge hex mesh on bottom<br />

over middle layer<br />

– metal beads on corners<br />

– joints taped<br />

• 1/16" veneer plaster finish<br />

– 2-1/2" concrete deck on fluted steel floor<br />

– 3.4 lb self-furring diamond mesh metal lath UL Des D403 Structural member tested: E-28<br />

enclosing beam W12 x 58<br />

• 1-1/2" 100:2 gypsum-perlite plaster Suitable for protection of beams and girders<br />

56 <strong>USG</strong> <strong>Fire</strong>-<strong>Resistant</strong> <strong>Assemblies</strong>