21.03.2013 Views

35 kV and Below INTERCONNECTION REQUIREMENTS - BC Hydro

35 kV and Below INTERCONNECTION REQUIREMENTS - BC Hydro

35 kV and Below INTERCONNECTION REQUIREMENTS - BC Hydro

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Revision Date: May 2010<br />

<strong>35</strong> <strong>kV</strong> <strong>and</strong> <strong>Below</strong> Interconnection Requirements for Power Generators<br />

conditions, the AVR for generators rated 5.0 MVA <strong>and</strong> up shall be capable of automatically maintaining the<br />

generator terminal voltage, without hunting, to within plus or minus 0.1% of any set point within an<br />

operating range between plus 20% <strong>and</strong> minus 30% of the rated terminal voltage of the generator. This<br />

control range is for testing purposes only <strong>and</strong> is not meant to require that the generator <strong>and</strong> excitation<br />

equipment have the capability to operate for any significant length of time at these terminal voltage levels.<br />

<strong>Hydro</strong>-electric generators may undergo large speed changes during a sudden load change. The voltage<br />

regulators for these generators must maintain a linear characteristic with voltage variations restricted to<br />

less than 5% when machine speed varies from minimum to maximum anticipated value.<br />

Induction Generator Resonance <strong>and</strong> Self-Excitation<br />

The PG owner should consider resonance in the design of the generation facility, as certain resonance<br />

can cause damage to electrical equipment, including the PG electrical equipment. Engineering analysis<br />

by the PG should be a part of the design process to evaluate the existence of, <strong>and</strong> to eliminate the harmful<br />

effects of ferroresonance in the PG transformer, <strong>and</strong> resonance with other customers' equipment due to<br />

the addition of shunt capacitor banks to the <strong>BC</strong>H distribution system.<br />

The adverse effects of self-excitation of the induction generator during isl<strong>and</strong> conditions must be assessed<br />

<strong>and</strong> mitigated. The intent is to detect <strong>and</strong> eliminate any self-excited condition. An engineering analysis of<br />

resonance <strong>and</strong> the assessment of the self-excitation effects of induction generators may be required by<br />

the PG.<br />

3.4.3 Speed Governors<br />

Synchronous generators rated < 1.0 MVA require a speed governor - typically a hydraulic flyball with no<br />

remote signal.<br />

Synchronous generators rated 1.0 MVA <strong>and</strong> up require a digital governor package on their prime movers.<br />

The frequency of the electric system is controlled by all synchronous generator governor systems that<br />

connect to the electric system. Governors must be operated unrestrained to regulate system frequency<br />

<strong>and</strong> to provide added system stability. Such governor systems respond automatically to changes in<br />

system frequency to prevent further deviation.<br />

Governors should be capable of operating in droop or isochronous mode as required. Governors in droop<br />

mode shall be set to provide a 5% droop characteristic, i.e. if the generator were isolated from the<br />

interconnected system <strong>and</strong> its loading were raised from zero to 100% of its rated MW output, the<br />

generator frequency should drop by 5% (from 60 Hz to 57 Hz). The governor shall not have a deadb<strong>and</strong><br />

of more than 0.056 Hz.<br />

The performance requirements for the governor system for operation in <strong>BC</strong>H should generally be in<br />

accordance with Section 4 of IEEE St<strong>and</strong>ard 125 "IEEE Recommended Practice for Preparation of<br />

Equipment Specifications for Speed Governing of Hydraulic Turbines Intended to Drive Electric<br />

Generators" <strong>and</strong> with Section 4 of IEEE St<strong>and</strong>ard 122 "IEEE Recommended Practice for Functional <strong>and</strong><br />

Performance Characteristics of Control Systems for Steam Turbine-Generator Units.” Similar performance<br />

requirements shall apply to all types of prime movers (including reciprocating combustion engines <strong>and</strong> gas<br />

turbines).<br />

3.4.4 Voltage <strong>and</strong> Frequency Operation During Disturbances<br />

Power system disturbances caused by system events such as faults <strong>and</strong> forced equipment outages<br />

expose connected generators to oscillations in voltage <strong>and</strong> frequency. It is important that larger<br />

synchronous generators remain in service for dynamic oscillations that are stable <strong>and</strong> damped.<br />

Over/under voltage <strong>and</strong> over/under frequency relays are installed to protect the generators <strong>and</strong> <strong>BC</strong>H<br />

customer loads from extended off-nominal operation. The required settings <strong>and</strong> time delays for these<br />

17

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!