Revision Date: May 2010<br />

<strong>35</strong> <strong>kV</strong> <strong>and</strong> <strong>Below</strong> Interconnection Requirements for Power Generators<br />

APPENDIX C PROTECTION COORDINATION EXAMPLE<br />

Figure C1 shows the typical overcurrent coordination between the PG entrance protection <strong>and</strong><br />

<strong>BC</strong> <strong>Hydro</strong> equipment, for a <strong>BC</strong> <strong>Hydro</strong> primary service with <strong>and</strong> without fuses.<br />

40