<strong>Cutler</strong>-<strong>Hammer</strong><br />

May 2001<br />

Indoor<br />

36-inch [914.4] Wide Typical<br />

Auxiliary/Breaker Vertical Section<br />

Medium-Voltage Distribution Equipment<br />

Metal-Clad Switchgear – Drawout Vacuum Breakers (VCP-W)<br />

Typical Units Available Configurations<br />

115.0<br />

[2921]<br />

Drawout<br />

V.T.S<br />

Breaker<br />

CTS<br />

H<br />

Gnd.<br />

Bus<br />

96.25 [2444.75]<br />

Breaker<br />

110.5 [2806.7]<br />

Drawout<br />

V.T.S<br />

CTS<br />

ARR<br />

Outdoor Aisleless<br />

Typical Auxiliary/Breaker Vertical Section<br />

H<br />

Main Bus<br />

Gnd.<br />

Bus<br />

101.5 [2568.45]<br />

Main Bus<br />

ARR<br />

H<br />

H<br />

H<br />

H<br />

95.00<br />

[2413]<br />

107.31<br />

[2725.67]<br />

Typical Weights, Lbs. (kg.)<br />

Assemblies (Less Breakers)<br />

Type of Main Bus Indoor Outdoor<br />

Vertical Rating<br />

Aisleless<br />

Section Amperes<br />

A/B 1200 2500 (1135) 3100 (1410)<br />

2000 2600 (1180) 3200 (1455)<br />

A/A 1200 2100 (955) 2700 (1230)<br />

2000 2200 (1000) 2800 (1275)<br />

Layout Dimensions – 27 kV<br />

H1<br />

Drawout<br />

Fuse<br />

Fixed<br />

CPT<br />

96.25 [2444.75]<br />

Main Bus<br />

Indoor<br />

36-inch [914.4] Wide Typical<br />

Auxiliary/Auxiliary Vertical Section<br />

Breaker Weights<br />

Type of<br />

Breaker<br />

270 VCPW 750<br />

270 VCPW 1000<br />

270 VCPW 1250<br />

270 VCPW 40<br />

H<br />

H<br />

95.00<br />

[2413]<br />

Current Rating, Amperes<br />

1200 2000<br />

415 (188)<br />

415 (188)<br />

415 (188)<br />

415 (188)<br />

475 (216)<br />

475 (216)<br />

475 (216)<br />

475 (216)<br />

Dimensions for Estimating Purposes Only.<br />

Drawout<br />

VTs<br />

1200-Amp<br />

Breaker<br />

Drawout<br />

Fuses<br />

Fixed<br />

CPT<br />

Drawout<br />

VTs<br />

2000-Amp<br />

Breaker<br />

[ ] = Dimensions in mm.<br />

B1-13<br />

Drawout<br />

VTs<br />

Drawout<br />

VTs