B1-16<br />

4.15" [105.41]<br />

16" [406.4]<br />

7.5" [190.5]<br />

2.20" [55.88]<br />

Medium-Voltage Distribution Equipment<br />

Metal-Clad Switchgear – Drawout Vacuum Breakers (VCP-W)<br />

3.75" [95.25]<br />

34.5" [876.3]<br />

Top View of Typical Indoor Breaker and Auxiliary<br />

Structures<br />

1 1 1<br />

3<br />

Layout Dimensions – 38 kV<br />

5 5 5 6<br />

MAXIMUM Hinged Panel Equipment<br />

➀<br />

Top Secondary<br />

Conduit Space<br />

3.38" [85.85]<br />

3" [76.2]<br />

7<br />

4<br />

4<br />

No devices on the<br />

breaker compartment<br />

door<br />

3.5" [88.9]<br />

Control<br />

Compt.<br />

Door<br />

1-Large Relay<br />

Case<br />

3-Instrument<br />

4-Test Switch<br />

5-Switch<br />

6-Lock-out<br />

Relay or<br />

Switch<br />

7-IQ Metering<br />

Unit<br />

Breaker<br />

Compt.<br />

Door<br />

4.15"<br />

[105.41]<br />

128.75" [3270.25]<br />

61.62" [1565.15]<br />

16"<br />

[406.4]<br />

65.85" [1672.59]<br />

30.88"<br />

[784.35]<br />

3" [76.2]<br />

➆<br />

➅<br />

42" [1066.8]<br />

3.75" [95.25]<br />

34.5" [876.3]<br />

1.48"<br />

[37.59]<br />

Base Plan of a Typical Indoor Breaker or Auxiliary<br />

Structure<br />

Dimensions for Estimating Purposes Only.<br />

➀<br />

39.60"<br />

[1005.84]<br />

➃ ➃<br />

➄<br />

12" [304.8]<br />

39.60"<br />

[1005.84]<br />

➃ ➃<br />

7.5" [190.5]<br />

15.38" [390.65]<br />

➇<br />

➁<br />

➂<br />

➂<br />

Front<br />

➈<br />

A<br />

Four Conduits<br />

7 [177.8]"<br />

Three Conduits<br />

Two Conduits<br />

B B<br />

C A<br />

Single Conduit<br />

<strong>Cutler</strong>-<strong>Hammer</strong><br />

7 [177.8]"<br />

9" [228.6]➉<br />

7 [177.8]"<br />

12" [304.8]<br />

May 2001<br />

A = 10" [254]<br />

B = 4.5" [114.3]<br />

C = 5.5" [139.7]<br />

9" [228.6]➉<br />

7 [177.8]"<br />

9" [228.6]➉<br />

7" [177.8]<br />

Primary Conduit Locations for Top or Bottom Entry<br />

[ ] = Dimensions in mm.<br />

➀ Primary conduit locations for top or bottom entry.<br />

➁ Recommended minimum clearance to rear of<br />

VacClad-W: 42 inches [1066.8].<br />

➂ Floor steel, if used, must not exceed 3.25 inches<br />

[82.55] under VacClad-W.<br />

➃ Anchor locations: indoor – 0.5-inch [13] bolts or<br />

weld, outdoor – 0.5-inch [13] bolts.<br />

➄ Station ground connection provision.<br />

➅ Secondary conduit space: All – maximum of<br />

1-inch [25.4] projection.<br />

➆ Minimum clearance to LH side of VacClad-W:<br />

38 inches [965.2].<br />

➇ Finished foundation surface (including floor<br />

steel) must be flat and level and in true plane.<br />

➈ Minimum clearance to front of VacClad-W:<br />

84 inches [2133.6].<br />

➉ Changes to 10.25 inches [260.35] if optional<br />

hinged rear doors are required.<br />

Note that the figure above shows that the<br />

arrangement of components. The figure may also<br />

be used to select custom arrangements of hinged<br />

panel components.<br />

Use of multipurpose solid-state relays such as the<br />

<strong>Cutler</strong>-<strong>Hammer</strong> Digitrip 3000 (same size as device<br />

7) will significantly reduce consumption of panel<br />

space. Changes to 13.25 inches [336.55] if optional<br />

hinged rear doors are required.