B1-16<br />
4.15" [105.41]<br />
16" [406.4]<br />
7.5" [190.5]<br />
2.20" [55.88]<br />
Medium-Voltage Distribution Equipment<br />
Metal-Clad Switchgear – Drawout Vacuum Breakers (VCP-W)<br />
3.75" [95.25]<br />
34.5" [876.3]<br />
Top View of Typical Indoor Breaker and Auxiliary<br />
Structures<br />
1 1 1<br />
3<br />
Layout Dimensions – 38 kV<br />
5 5 5 6<br />
MAXIMUM Hinged Panel Equipment<br />
➀<br />
Top Secondary<br />
Conduit Space<br />
3.38" [85.85]<br />
3" [76.2]<br />
7<br />
4<br />
4<br />
No devices on the<br />
breaker compartment<br />
door<br />
3.5" [88.9]<br />
Control<br />
Compt.<br />
Door<br />
1-Large Relay<br />
Case<br />
3-Instrument<br />
4-Test Switch<br />
5-Switch<br />
6-Lock-out<br />
Relay or<br />
Switch<br />
7-IQ Metering<br />
Unit<br />
Breaker<br />
Compt.<br />
Door<br />
4.15"<br />
[105.41]<br />
128.75" [3270.25]<br />
61.62" [1565.15]<br />
16"<br />
[406.4]<br />
65.85" [1672.59]<br />
30.88"<br />
[784.35]<br />
3" [76.2]<br />
➆<br />
➅<br />
42" [1066.8]<br />
3.75" [95.25]<br />
34.5" [876.3]<br />
1.48"<br />
[37.59]<br />
Base Plan of a Typical Indoor Breaker or Auxiliary<br />
Structure<br />
Dimensions for Estimating Purposes Only.<br />
➀<br />
39.60"<br />
[1005.84]<br />
➃ ➃<br />
➄<br />
12" [304.8]<br />
39.60"<br />
[1005.84]<br />
➃ ➃<br />
7.5" [190.5]<br />
15.38" [390.65]<br />
➇<br />
➁<br />
➂<br />
➂<br />
Front<br />
➈<br />
A<br />
Four Conduits<br />
7 [177.8]"<br />
Three Conduits<br />
Two Conduits<br />
B B<br />
C A<br />
Single Conduit<br />
<strong>Cutler</strong>-<strong>Hammer</strong><br />
7 [177.8]"<br />
9" [228.6]➉<br />
7 [177.8]"<br />
12" [304.8]<br />
May 2001<br />
A = 10" [254]<br />
B = 4.5" [114.3]<br />
C = 5.5" [139.7]<br />
9" [228.6]➉<br />
7 [177.8]"<br />
9" [228.6]➉<br />
7" [177.8]<br />
Primary Conduit Locations for Top or Bottom Entry<br />
[ ] = Dimensions in mm.<br />
➀ Primary conduit locations for top or bottom entry.<br />
➁ Recommended minimum clearance to rear of<br />
VacClad-W: 42 inches [1066.8].<br />
➂ Floor steel, if used, must not exceed 3.25 inches<br />
[82.55] under VacClad-W.<br />
➃ Anchor locations: indoor – 0.5-inch [13] bolts or<br />
weld, outdoor – 0.5-inch [13] bolts.<br />
➄ Station ground connection provision.<br />
➅ Secondary conduit space: All – maximum of<br />
1-inch [25.4] projection.<br />
➆ Minimum clearance to LH side of VacClad-W:<br />
38 inches [965.2].<br />
➇ Finished foundation surface (including floor<br />
steel) must be flat and level and in true plane.<br />
➈ Minimum clearance to front of VacClad-W:<br />
84 inches [2133.6].<br />
➉ Changes to 10.25 inches [260.35] if optional<br />
hinged rear doors are required.<br />
Note that the figure above shows that the<br />
arrangement of components. The figure may also<br />
be used to select custom arrangements of hinged<br />
panel components.<br />
Use of multipurpose solid-state relays such as the<br />
<strong>Cutler</strong>-<strong>Hammer</strong> Digitrip 3000 (same size as device<br />
7) will significantly reduce consumption of panel<br />
space. Changes to 13.25 inches [336.55] if optional<br />
hinged rear doors are required.