Fault finding<br />
Description: Lack of water (only for pump<br />
equipped with SensorLogic)<br />
Corrective action: Fill-up the water circuit<br />
Description: Main heat exchanger frozen<br />
Corrective action: Carefully de-frost the exchanger<br />
Code: Description: Intervention of the high limit<br />
thermostat (TL)<br />
Code:<br />
Description: Modulating fan failure<br />
Corrective action: Check the fan’s wiring<br />
Description: Modulating fan failure<br />
Corrective action: Check the fan’s wiring<br />
Corrective action: Press the reset key on the<br />
control panel<br />
Description: Heating sensor failure<br />
Corrective action: Check the sensor’s efficiency<br />
and/or wiring<br />
Code: Description: Alteration of the operating<br />
parameters caused by EMC disturbances<br />
Corrective action: Restore the factory parameters<br />
Code: Description: Flame signal detected before the<br />
ignition cycle<br />
Corrective action: Disconnect the detection<br />
electrode’s wire from the control board; if the error<br />
code disappears replace the cable, otherwise<br />
replace the control board.<br />
Code: Description: Flame detected after burner OFF<br />
Code:<br />
Corrective action: Disconnect the gas valve’s wire<br />
from the control board; if the error code<br />
disappears replace the control board, otherwise<br />
replace the gas valve.<br />
Description: Internal failure<br />
Corrective action: Replace the control board<br />
5.2 - REQUEST OF MAINTENANCE<br />
The boiler has an integrated system that, after 10.000<br />
switching On or 2.000 hours of operation of the burner,<br />
provides to signal that the boiler needs maintenance.<br />
Such information is indicated on the display by the lighting<br />
of the code .<br />
The flashing of the code doesn’t inhibit the<br />
normal operation of the boiler.<br />
Service the appliance and subsequently reset the counter<br />
by selecting “Cr” from the parameters menù and introducing<br />
the relevant resetting code.