5.3 - DISPLAY OF ERROR CODES ON HEATING CONTROLLER E8<br />
Code: Description:<br />
Air in the pump (only for pump with Sensor<br />
Logic<br />
E 41<br />
Corrective action:<br />
Manually bleed the air from the circuit<br />
Code: Description:<br />
DHW sensor failure (SS) (only if the boiler is combined<br />
with an external D.H.W. tank)<br />
E 13 E 14<br />
Code:<br />
E 32<br />
E 2<br />
E 15<br />
E 42<br />
18<br />
24<br />
12<br />
6<br />
Corrective action:<br />
Check the sensor’s efficiency and/or its wiring<br />
Code: Description:<br />
Insufficient gas pressure<br />
Corrective action:<br />
Check the pressure, if the pressure is correct<br />
control the gas switch and/or its wiring.<br />
Code: Description:<br />
Difference between the temperature of the CH<br />
sensor (SR) and the temperature of the heating<br />
return sensor (SRR) > 35°C.<br />
Code:<br />
Description:<br />
Mains supply < 190 Vac<br />
Corrective action:<br />
Check that the mains supply is < 190Vac. If the<br />
mains supply is correct replace the control board.<br />
Corrective action:<br />
Examine the system.<br />
Description:<br />
Jammed pump (only for pump with<br />
SensorLogic)<br />
Corrective action:<br />
After removal of the central plug of the pump<br />
body turn with a screw driver the pump rotor<br />
and replace the plug.<br />
Fault finding<br />
In case of fault, on the display of the regulator a blinking triangle<br />
with its error code will appear<br />
Here below you will find the E8 error codes, the relevant<br />
meaning and corrective actions.<br />
For the error codes related to the heating system, make<br />
reference to the paragraph “Fault finding” of the “User<br />
Instruction manual” supplied with the E8.<strong>50</strong>64 heating<br />
controller.<br />
Codice: Description:<br />
Failure on the pump wiring (only for pump with<br />
SensorLogic)<br />
E 43<br />
Code:<br />
Code:<br />
E 40<br />
Code:<br />
E 6<br />
Code:<br />
E 5<br />
Code:<br />
E 4<br />
Corrective action:<br />
Verify the wiring<br />
Description:<br />
Failure of the heating return sensor (SRR)<br />
Corrective action:<br />
Check the efficiency of the sensor and/or its wiring<br />
Description:<br />
Bad water circulation<br />
Corrective action:<br />
Examine the system<br />
Description:<br />
Water temperature too high detected by the CH<br />
sensor (SR) (>95°C)<br />
Corrective action:<br />
Check adequate flow of water through boiler<br />
Description:<br />
Loss of flame signal during boiler operation<br />
Corrective action:<br />
Press the reset button on the control panel<br />
Description:<br />
No flame detected during the ignition phase<br />
Corrective action:<br />
Press the reset button on the control panel<br />
59