5.3 - DISPLAY OF ERROR CODES ON HEATING CONTROLLER E8<br />

Code: Description:<br />

Air in the pump (only for pump with Sensor<br />

Logic<br />

E 41<br />

Corrective action:<br />

Manually bleed the air from the circuit<br />

Code: Description:<br />

DHW sensor failure (SS) (only if the boiler is combined<br />

with an external D.H.W. tank)<br />

E 13 E 14<br />

Code:<br />

E 32<br />

E 2<br />

E 15<br />

E 42<br />

18<br />

24<br />

12<br />

6<br />

Corrective action:<br />

Check the sensor’s efficiency and/or its wiring<br />

Code: Description:<br />

Insufficient gas pressure<br />

Corrective action:<br />

Check the pressure, if the pressure is correct<br />

control the gas switch and/or its wiring.<br />

Code: Description:<br />

Difference between the temperature of the CH<br />

sensor (SR) and the temperature of the heating<br />

return sensor (SRR) > 35°C.<br />

Code:<br />

Description:<br />

Mains supply < 190 Vac<br />

Corrective action:<br />

Check that the mains supply is < 190Vac. If the<br />

mains supply is correct replace the control board.<br />

Corrective action:<br />

Examine the system.<br />

Description:<br />

Jammed pump (only for pump with<br />

SensorLogic)<br />

Corrective action:<br />

After removal of the central plug of the pump<br />

body turn with a screw driver the pump rotor<br />

and replace the plug.<br />

Fault finding<br />

In case of fault, on the display of the regulator a blinking triangle<br />

with its error code will appear<br />

Here below you will find the E8 error codes, the relevant<br />

meaning and corrective actions.<br />

For the error codes related to the heating system, make<br />

reference to the paragraph “Fault finding” of the “User<br />

Instruction manual” supplied with the E8.<strong>50</strong>64 heating<br />

controller.<br />

Codice: Description:<br />

Failure on the pump wiring (only for pump with<br />

SensorLogic)<br />

E 43<br />

Code:<br />

Code:<br />

E 40<br />

Code:<br />

E 6<br />

Code:<br />

E 5<br />

Code:<br />

E 4<br />

Corrective action:<br />

Verify the wiring<br />

Description:<br />

Failure of the heating return sensor (SRR)<br />

Corrective action:<br />

Check the efficiency of the sensor and/or its wiring<br />

Description:<br />

Bad water circulation<br />

Corrective action:<br />

Examine the system<br />

Description:<br />

Water temperature too high detected by the CH<br />

sensor (SR) (>95°C)<br />

Corrective action:<br />

Check adequate flow of water through boiler<br />

Description:<br />

Loss of flame signal during boiler operation<br />

Corrective action:<br />

Press the reset button on the control panel<br />

Description:<br />

No flame detected during the ignition phase<br />

Corrective action:<br />

Press the reset button on the control panel<br />