Power OFF Operation Section 10-3<br />

Operating Mode Changes and I/O Memory<br />

Mode Changes Non-holding areas Holding Areas<br />

I/O bits<br />

HR Area<br />

Data Link bits<br />

DM Area<br />

CPU Bus Unit bits<br />

EM Area<br />

Special I/O Unit bits<br />

Counter PV and Completion Flags<br />

Inner Board bits<br />

SYSMAC BUS bits<br />

I/O Terminal bits<br />

C200H Special I/O Unit bits<br />

DeviceNet bits<br />

Work bits<br />

Timer PV/Completion Flags<br />

Index Registers<br />

Data Registers<br />

Task Flags<br />

(Auxiliary Area bits/words are holding<br />

or non-holding depending on the<br />

address.)<br />

(Auxiliary Area bits/words are holding<br />

or non-holding depending on the<br />

address.)<br />

RUN or MONITOR to PROGRAM Cleared (See note 1.) Held<br />

PROGRAM to RUN or MONITOR Cleared (See note 1.) Held<br />

RUN to MONITOR or<br />

MONITOR to RUN<br />

Held (See note 2.) Held<br />

486<br />

Note 1. The following processing is performed depending on the status of the I/O<br />

Memory Hold Bit. Output from Output Units will be turned OFF when operation<br />

stops even if I/O bit status is held in the CPU Unit.<br />

2. The cycle time will increase by approximately 10 ms when the operating<br />

mode is changed from MONITOR to RUN mode. This will not, however,<br />

cause an error for exceeding the maximum cycle time limit.<br />

I/O Memory<br />

I/O Memory Output bits allocated to Output Units<br />

Hold Bit status<br />

(A50012)<br />

Mode changed<br />

between<br />

PROGRAM<br />

and RUN/<br />

MONITOR<br />

Operation stopped<br />

Fatal error FALS<br />

other than executed<br />

FALS<br />

Mode changed<br />

between<br />

PROGRAM<br />

and RUN/<br />

MONITOR<br />

Operation stopped<br />

Fatal error FALS<br />

other than executed<br />

FALS<br />

OFF Cleared Cleared Held OFF OFF OFF<br />

ON Held Held Held Held OFF OFF<br />

10-3 Power OFF Operation<br />

10-3-1 Overview<br />

Note Refer to 9-2 I/O Memory Areas for more details on I/O Memory.<br />

The following processing is performed if CPU Unit power is turned OFF.<br />

Power OFF processing will be performed if the power supply falls below 85%<br />

of the rated voltage while the CPU Unit is in RUN or MONITOR mode.<br />

1,2,3... 1. The CPU Unit will stop.<br />

2. Outputs from all Output Units will be turned OFF.