Auxiliary Area Appendix B<br />

Address Name Function Status Status at Write timing/<br />

Words Bits<br />

after<br />

mode<br />

change<br />

startup Related flags,<br />

settings<br />

Cleared Cleared A40210<br />

A406 All PLC Setup<br />

Error Location<br />

A407 A40700<br />

to<br />

A40712<br />

726<br />

A40713<br />

to<br />

A40715<br />

Too Many<br />

I/O Points,<br />

Details<br />

Too Many<br />

I/O Points,<br />

Cause<br />

When there is a setting error in the PLC Setup, the<br />

location of that error is written to A406 in 4-digit hexadecimal.<br />

The location is given as the address displayed<br />

on a Programming Console.<br />

The CPU Unit will continue operating and the<br />

ERR/ALM indicator on the front of the CPU Unit will<br />

flash.<br />

0000 to 01FF hexadecimal<br />

(A406 will be cleared when the cause of the error is<br />

eliminated.)<br />

The 6 possible causes of the Too Many I/O Points<br />

Error are listed below. The 3-digit binary value in<br />

A40713 to A40715 indicates the cause of the error<br />

(values 0 to 5 correspond to causes 1 to 6, below).<br />

The 13-bit binary value in A40700 to A40712 indicates<br />

the details: the excessive value or the duplicated unit<br />

number.<br />

CPU Unit operation will stop and the ERR/ALM indicator<br />

on the front of the CPU Unit will light.<br />

1) The number of I/O points will be written here when<br />

the total number of I/O points set in the I/O Table<br />

(excluding Slave Racks) exceed the maximum<br />

allowed for the CPU Unit.<br />

2) The number of interrupt inputs will be written here<br />

when there are more than 32 interrupt inputs.<br />

3) The unit number of the Slave Unit will be written<br />

here when a unit number is duplicated or the number<br />

of I/O points on a C500 Slave Unit exceeds 320.<br />

4) The unit number of the I/O Terminal (excluding<br />

Slave Racks) will be written here when a unit number<br />

is duplicated.<br />

5) The unit number of the Master Unit will be written<br />

here when a unit number is duplicated or the unit<br />

number is outside of the allowed setting range.<br />

6) The number of Racks will be written here when the<br />

number of Expansion I/O Racks exceeds the maximum.<br />

(The relevant value will be written here (A40700 to<br />

A40712) when the error occurs. These bits will be<br />

cleared when the error is cleared.)<br />

The 3-digit binary value of these bits indicates the<br />

cause of the Too Many I/O Points Error and shows the<br />

meaning of the value written to bits A40700 to<br />

A40712.<br />

Values of 000 to 101 (0 to 5) correspond to causes 1<br />

through 6 described in “Too Many I/O Points, Cause 1,”<br />

above.<br />

000: Too many I/O total<br />

001: Too many interrupt I/O<br />

010: Duplicate Remote I/O Slave Unit unit numbers or<br />

too many I/O on C500 Remote I/O Slave Units<br />

(more than 320)<br />

011: Duplicate I/O Terminal unit numbers<br />

100: Duplicate Remote I/O Master Unit unit numbers<br />

or undefined unit numbers (not 0 or 1)<br />

101: Too many Racks<br />

(These bits will be cleared when the error is cleared.)<br />

Cleared Cleared A40111, A40713 to<br />

A40715<br />

Cleared Cleared ---