OR 2 Internal Loads<br />
Load name Ext. Voltage Amps Percentage Watts Usage Effective Wattage Sensible btu/h Latent btu/h<br />
anesthia machine 1 120 13.5 66% 1,076 100% 1,076 3,670 0<br />
Pix 1 120 3 28% 100 100% 100 341 0<br />
Computer 5 120 9.0 26% 275 100% 275 938 0<br />
Blood Refrigerator 1 120 1.5 41% 73 100% 73 250 0<br />
Bovie 1 120 7.1 44% 377 10% 38 128 0<br />
fluid warmer 1 120 1 32% 38 100% 38 130 0<br />
microscope 1 120 2.75 19% 63 100% 63 215 0<br />
unknown load machine 1 120 12 36% 525 100% 525 1,793 100%<br />
People (active) 5 1,250 1,500<br />
Patient 1 225 105<br />
Lighting 5 480 100% 480 1,638 0 Total<br />
TOTAL 10,578 1,606 12,184<br />
2-22 Kaiser OR Loads rev2 Project No. 09104<br />
Page 17