Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
OR 6 Internal Loads<br />
Load name Ext. Voltage Amps Percentage Watts Usage Effective Wattage Sensible btu/h Latent btu/h<br />
anesthia machine 1 120 13.5 66% 1,076 100% 1,076 3,670 0<br />
profusion 1 120 1.5 19% 35 100% 35 119 0<br />
profusion 2 1 120 1.6 19% 37 100% 37 127 0<br />
Pix 1 120 3 28% 100 100% 100 341 0<br />
Computer 7 120 12.6 26% 385 100% 385 1,314 0<br />
Blood Refrigerator 1 120 1.5 41% 73 100% 73 250 0<br />
digital recording tower 1 120 12.43333333 11% 163 100% 163 555 0<br />
Data Manager 1 120 4.4 26% 135 100% 135 460 1<br />
Ultrasound 1 120 15 80% 1,440 100% 1,440 4,913 0<br />
cardiac monitor 1 120 6 57% 408 100% 408 1,392 0<br />
Warmer 1 120 12 32% 456 100% 456 1,556 0<br />
blanket pump 1 120 6.666666667 44% 354 100% 354 1,206 0<br />
Bovie 2 250 4 44% 884 10% 88 302 0<br />
josturn 1 120 18 3% 75 100% 75 256 0<br />
Datascope 1 120 4.1 19% 94 100% 94 320 0<br />
Headlight 1 120 3.0 100% 360 100% 360 1,228 0<br />
Eye Machine 1 120 8.3 15% 147 100% 147 502 0<br />
Monitor 3 120 3.6 24% 305 100% 305 1,042 0<br />
People (active) 7 1,750 2,100<br />
Patient 1 225 105<br />
Lighting 20 960 100% 960 3,276 0 Total<br />
TOTAL 24,805 2,206 27,011<br />
2-22 Kaiser OR Loads rev2 Project No. 09104<br />
Page 24